iManager NetEco 6000
Device Installation and Commissioning Guide
6 Adding Devices
Issue 03 (2019-03-10)
Copyright © Huawei Technologies Co., Ltd.
192
Parameter
Description
Authentication
Protocol
Set this parameter to the authentication protocol set on the device.
The default selection is
SHA
.
Support
SHA
and
MD5
agreement.
Authentication
Password
Set this parameter to the
SHA
or
MD5
password set on the device.
Privacy Protocol
Set this parameter to the privacy protocol set on the device. The
default selection is
AES128
.
Support
CBC_DES
,
AES128
,
AES192
, and
AES256
agreement.
Privacy Password
Set this parameter to the
AES
or
DES
password set on the device.
NOTE
You are advised to set
Authentication Password
and
Privacy Password
to
different values.
Timeout period
Timeout duration for connection test (set to
3s
by default)
Step 8
Click
Connection Test
to start the connection test.
Step 9
After the connection test is successful, click
in the toolbar to save the device
information.
----End
6.4.2 Adding Sensors
6.4.2.1 Adding Dry Contact Interface Devices
6.4.2.1.1 Setting Door Status Sensor Monitoring Parameters on the ECC
After connecting a door status sensor (DSS) to the AI/DI port of an ECC500 V6 collector, you
need to set DSS parameters on the web user interface (WebUI) of the collector.
Prerequisites
You have obtained the IP address, and login user name and password for the ECC500 V6
collector.
A PC with an IP address in the same network segment as the ECC500 V6 collector is
prepared, and the PC has been connected to the ECC500 V6 collector over a switch.
Context
This section describes how to set DSS monitoring parameters when a DSS is connected to the
AI/DI_1 port of the MUE05A4 card of an ECC500 V6 collector. Set the parameters based on
the actual port connected to the DSS onsite.
Procedure
Step 1
Log in to the WebUI of the ECC500 V6 collector.