iManager NetEco 6000
Device Installation and Commissioning Guide
4 Connecting Monitoring Cables to Devices
Issue 03 (2019-03-10)
Copyright © Huawei Technologies Co., Ltd.
98
Table 4-19
Indicator light definition
Terminal Identity
Definition
P
The controller power light, red
RUN
Controller working indicator light, white blue, flashing
LK(1-4)
Lock status indicator light
Table 4-20
RS485 interface
Terminal Identity
Definition
AL3(A8802RS)/AL5(A8
804RS)
RS485-A
Gnd
RS485-B
Table 4-21
Access control system cable list
BOM
Number
BOM Description
Cable Position
25030384
Electric Cable, 300V/500V, 60227 IEC
53(RVV), 3x1mm
2
, Black(3Cores: Brown,
Blue, Yellow/Green), 10A, Outdoor Cable,
CCC, CE
Access controller power cable
25030641
Electric Cable, 300V, UL2464, 4x20AWG,
Black(4Cores: Yellow, Green, Violet,
White), 9A, Non-shielding Outdoor Cable,
UL
Cable from the magnetic lock
to the access controller
25030393
Electric Cable, 300V/500V, 60227 IEC
53(RVV), 2x0.75mm
2
, Black(2Cores:
Brown, Blue), 6A, Flat Outdoor Cable,
CCC, CE
Cable from the emergency
door release button to the
access controller
14180327
Terminal Block, 4-Pin, Screw Fixed, 24–12
AWG, Pitch 5.08 mm, Male and Female
Using Together, Only for Power Supply
25031053
Electric Cable, 300V, UL2464, 7x20AWG,
Black(7Cores: Red, Black, Yellow, Green,
Orange, White, Blue), 9A, Non-shielding
Cable, UL
Cable from the card reader to
the access controller
14180327
Terminal Block, 4-Pin, Screw Fixed, 24–12
AWG, Pitch 5.08 mm, Male and Female
Using Together, Only for Power Supply