iManager NetEco 6000
Device Installation and Commissioning Guide
6 Adding Devices
Issue 03 (2019-03-10)
Copyright © Huawei Technologies Co., Ltd.
196
Step 2
Choose
Monitoring
>
MUE05A Expansion Card
>
MUE05A4
>
Running Parameter
>
AI/DI_1 Port Settings
.
Step 3
Select
Enable
for
AI/DI_1 Sensor
.
Step 4
Click
Submit
, as shown in
Figure 6-57
Setting port enabling of a dry contact
Step 5
Select
NO
or
NC
for
AI/DI_1 Sensor Type
from the drop-down list, as shown in
Figure 6-58
Setting the sensor type of a dry contact
NO: indicates a normally open dry contact. The dry contact will report an alarm in the normally
closed state.
NC: indicates a normally closed dry contact. The dry contact will report an alarm in the normally
open state.