iManager NetEco 6000
Device Installation and Commissioning Guide
6 Adding Devices
Issue 03 (2019-03-10)
Copyright © Huawei Technologies Co., Ltd.
230
Parameter
Description
Out Time
Timeout duration for connection test (set to
3s
by default)
Step 7
Click
Connection Test
to start the connection test.
Step 8
After the connection test is successful, click
in the toolbar to save the device
information.
----End
6.4.4 Adding a Smart Cooling Product
6.4.4.1 Setting Monitoring Parameters for NetCol5000 and NetCol8000(over
Modbus-RTU)
The method of setting monitoring parameters for NetCol5000C-65kW&80kW,
NetCol5000-C025/C030/A020/A035, NetCol8000-A050A100/C070/C150 are the same. This
section describes the configuration method for the NetCol5000.
Prerequisites
The device address planned for the NetCol5000 is obtained.
The NetCol5000 is powered on.
The IP address, user name, and password for logging in to the collector are obtained.
A PC with an IP address in the same network segment as the collector is prepared, and
the PC connects to the collector over a switch.
Context
Before connecting the NetCol5000 to the NetEco, set monitoring parameters, such as the
device address and baud rate, on the NetCol5000, and then modify the port parameters for the
collector connecting to the NetCol5000 to ensure that the values of
BaudRate
,
DataBit
,
StopBit
, and
Parity
on the NetCol5000 are consistent with those for the collector port.
Procedure
Step 1
On the display panel of the NetCol5000, press
Settings
.
Step 2
Enter the administrators password for the NetCol5000, then press
.
The NetCol5000 preset user name is
Admin
, and the password is
000001
. To protect the access security,
change the password after logging in to the NetCol5000 for the first time.
Step 3
Press
Comm Settings
.
Step 4
Set
Baud Rate
and
Com address
.