iManager NetEco 6000
Device Installation and Commissioning Guide
6 Adding Devices
Issue 03 (2019-03-10)
Copyright © Huawei Technologies Co., Ltd.
166
Figure 6-36
Setting SNMP parameters_03
8.
Set
Trap Address
to the IP address of the NetEco server, and set
Trap Port
to
162
.
9.
Click
Submit
.
Step 3
Optional:
If a CIM is configured for the UPS5000, verify that the UPS5000 and CIM
communications addresses are unique.
1.
Log in to the UPS5000 WebUI.
2.
Choose
Monitoring
>
Comm. Config.
>
RS485 Settings
, and verify that
Address
is set
to
1
for the UPS5000.
3.
Choose
Monitoring
>
CIM Param.
>
Basic Param.
, and verify that
CIM logical start
addr
is set to
2
for the UPS5000.
----End
6.3.4.3 Setting UPS5000 Monitoring Parameters (over Modbus TCP)
Prerequisites
You have obtained the IP address, subnet mask, and default gateway planned for the
UPS5000.
The UPS5000 is powered on.
Context
Before connecting the UPS5000 to the NetEco, set monitoring parameters, such as the IP
address, on the UPS5000.