GK600 User Manual Chapter 6 Specification of Parameters
-
225 -
H0-00
SCI port selection
Range: 0~1
Factory default: 0
0: Local 485 port
1: Optional 232 port
H0-01
SCI port communication
configuration
Range: 0000
~
1155
Factory default:
0001
Ones place: baud rate
0: 4800bps
1: 9600bps
2: 19200bps
3: 38400bps
4: 57600bps
5: 115200bps
Tens place: data format
0: 1-8-2-N format, RTU
1: 1-8-1-E format, RTU
2: 1-8-1-O format, RTU
3: 1-7-2-N format, ASCII
4: 1-7-1-E format, ASCII
5: 1-7-1-O format, ASCII
Hundreds place: connection type
0: Direct cable connection (232/485)
1: MODEM (232) (reserved)
Thousands place: communication data handling at power loss
0: Saved at power loss
1: Not saved at power loss
H0-02
Local address of SCI port
communication
Range: 0~247
Factory default: 5
Sets the local address. 0 is broadcast address, while available addresses are 1~247.
H0-03
Time out detection of SCI port
communication
Range: 0.0s~1000.0s
Factory default:
0.0s
This parameter sets communication error detection time. When it's set to 0, no communication
error will be reported.
H0-04
Time delay of SCI port
communication
Range: 0ms~1000ms
Factory default:
0ms
Sets time delay of this drive response to the master.