GK600 User Manual
Chapter 5 List of Parameters
- 105 -
Parameter
Designation
Scope
Factory
default
Attr
H0-07
Proportional factor of
received FREQ
0.0
~
1000.0%
100.0%
△
Group H1 Profibus-DP Communication Parameters
H1-00 Local address
1~126; 127
is broadcast address
4
△
H1-01 PPO type
0: Profibus disabled
1: PPO1
2: PPO2
3: PPO3
4: PPO4
5: PPO5
0
△
H1-02
PZD2_OUT(the master →
the slave)
0: none
0x6200~0x6214
0
△
H1-03
PZD3_OUT(the master →
the slave)
0: none
0x6200~0x6214
0
△
H1-04
PZD4_OUT(the master →
the slave)
0: none
0x6200~0x6214
0
△
H1-05
PZD5_OUT(the master →
the slave)
0: none
0x6200~0x6214
0
△
H1-06
PZD6_OUT(the master →
the slave)
0: none
0x6200~0x6214
0
△
H1-07
PZD7_OUT(the master →
the slave)
0: none
0x6200~0x6214
0
△
H1-08
PZD8_OUT(the master →
the slave)
0: none
0x6200~0x6214
0
△
H1-09
PZD9_OUT(the master →
the passive)
0: none
0x6200~0x6214
0
△
H1-10
PZD10_OUT(the master →
the slave)
0: none
0x6200~0x6214
0
△
H1-11
PZD2_IN(the slave → the
master)
0: none
A0-00~U2-xx
0x6200~0x6214
;
0x6300~0x6323
0
△
H1-12
PZD3_IN(the slave → the
master)
0: none
A0-00~U2-xx
;
0x6200~0x6214
;
0x6300~0x6323
0
△