Chapter 6 Specification of Parameters GK600 User Manual
- 134 -
interface of drive. Refer to parameters Group H0 and appendix for further information about
programming.
Run command from control panel, terminals and communication can be switched by terminals
"run command switched to control panel control", "run command switched to terminal control"
and "run command switched to communication control".
Multifunction key MF can be set to "run command sources shifted" key through parameter
L0-00. When MF key is pressed under this setting, run command will be shifted during control
panel control, terminal control and communication control circularly.
b1-01
Binding of run command
and frequency set
Range: 000 ~ AAA
Factory default:
000
This parameter defines the bundled combination of three run command sources and frequency
set with the purpose of facilitating simultaneous switching. For example: frequency setting AI1
(ones place of b1-01 is set to 3) bundled with control panel control, while the frequency setting
X6/DI pulse input (ten's place of b1-01 is set to 6) bundled with terminal control. In such a case,
when run command is controlled by control panel, frequency setting would be AI1, while when
run command is controlled via terminals, frequency setting will be automatically switched to
X6/DI pulse input.
Ones place: frequency setting bundled under control panel control
0: No binding
1: Digital setting (b0-02) +
∧
/
∨
adjustment on control panel
2: Digital setting (b0-02) + terminal UP/DOWN adjustment
3: Analog input AI1
4:Aanalog input AI2
5: Analog input EAI (on IO option board)
6: X6/DI pulse input
7: Process PID output
8: Simple PLC
9: Multi-step frequency
A: Communication input
Refer to parameter b0-01 for details regarding above-mentioned sources of frequency setting.
Tens place: frequency setting bundled under terminal control (same as ones place)
Hundreds place: frequency setting bundled under communication control (same as ones
place)
ATTENTION:
Different run command sources can be bundled with the same frequency setting source. The
priority of frequency setting sources bundled with run command overrides Group b0.