GK600 User Manual
Chapter 3 Installation and Wiring
- 39 -
■GK600-4T
G/
L
Three-phase 400V input
Drive model
Power terminal
Ground terminal
Cable
requiremen
t (mm
2
)
Screw
Torque
(kgf.cm)
Cable
requireme
nt (mm
2
)
Screw
Torque
(kgf.cm)
GK600-4T0.75G/1.5LB
0.75G
2.5
M3.5 10±0.5
2.5
M3.5
10±0.5
1.5L
2.5
2.5
GK600-4T1.5G/2.2LB
1.5G
2.5
M3.5 10±0.5
2.5
M3.5
10±0.5
2.2L
2.5
2.5
GK600-4T2.2G/3.7LB
2.2G
2.5
M4
14±0.5
2.5
M4
14±0.5
3.7L
2.5
2.5
GK600-4T3.7G/5.5LB
3.7G
2.5
M4
14±0.5
2.5
M4
14±0.5
5.5L
2.5
2.5
GK600-4T5.5G/7.5LB
5.5G
2.5
M4
14±0.5
2.5
M4
14±0.5
7.5L
4
4
GK600-4T7.5G/11LB
7.5G
4
M4
14±0.5
4
M4
14±0.5
11L
4
4
GK600-4T11G/15LB
11G
4
M5
28±0.5
4
M4
14±0.5
15L
6
6
GK600-4T15G/18.5LB
15G
6
M5
28±0.5
6
M4
14±0.5
18.5L
10
10
GK600-4T18.5G/22L(B)
18.5G
10
M6
48±0.5
10
M6
48±0.5
22L
10
10
GK600-4T22G/30L(B)
22G
10
M6
48±0.5
10
M6
48±0.5
30L
16
16
GK600-4T30G/37L(B)
30G
16
M6
48±0.5
16
M6
48±0.5
37L
25
16
GK600-4T37G/45L(B)
37G
25
M8
120
±0.5
16
M8
120±0.5
45L
35
16
GK600-4T45G/55L(B)
45G
35
M8
120
±0.5
16
M8
120±0.5
55L
50
25
GK600-4T55G/75L(B)
55G
50
M10
250
±0.5
25
M8
120±0.5
75L
70
35
GK600-4T75G/90L(B)
75G
70
M10
250
±0.5
35
M8
120±0.5
90L
95
50
GK600-4T90G/110L
90G
95
M12
440
±0.5
50
M12
440±0.5
110L
120
70