GK600 User Manual Chapter 6 Specification of Parameters
-
233 -
U0-30 Cumulative power-up time
Range: 0h~65535h
Factory default:
0h
U0-31 Cumulative run time
Range: 0h~65535h
Factory default:
0h
U0-32 Heat sink temperature 1
Range: -40.0
℃
~100.0
℃
Factory default:
0.0
℃
U0-33 Heat sink temperature 2
Range: -40.0
℃
~100.0
℃
Factory default:
0.0
℃
U0-34
U0-34
Range: 0~6
Factory default: 0
When the drive reports fault "FAL", the fault source can be known by U0-34.
0: No fault source
1: IGBT overcurrent
2: Reserved
3: Output grounding fault
4: Output overcurrent
5: DC bus overvoltage
6: Other sources
U0-35 Terminal count value
Range: 0~65535
Factory default: 0
U0-36 Run command log at LoU
Range: 0~1
Factory default: 0
U0-37 Fault code log at LoU
Range: 0~100
Factory default: 0
U0-38 Reserved
Reserved
Reserved
U0-39 CtC fault source
Range: 0~3
Factory default: 0
0: No fault
1: U-phase current detection circuit fault
2: V-phase current detection circuit fault
3: W-phase current detection circuit fault
U0-40
Higher-bit numbers of
actual length
Range: 0~65
Factory default: 0
U0-41
Lower-bit numbers of
actual length
Range: 0~65535
Factory default: 0
U0-42
Higher-bit numbers of
control panel
∧
/
∨
stored
value
Range: -1~1
Factory default: 0
U0-43
Lower-bit numbers of
control panel
∧
/
∨
stored
value
Range: 0.00~655.35Hz
Factory default:
0.00Hz