Chapter 6 Specification of Parameters GK600 User Manual
- 132 -
b0-12
Time-delay of stop when set
FREQ lower than lower limit
FREQ
Range: 0.0s~6553.5s
Factory default:
0.0s
When b0-11 is set to 2, and frequency setting is lower than lower limit frequency, the drive will
stop running after this parameter value.
b0-13
Lower limit of skip FREQ
band 1
Range: 0.00Hz ~ upper limit
frequency
Factory default:
0.00Hz
b0-14
Upper limit of skip FREQ
band 1
Range: 0.00Hz ~ upper limit
frequency
Factory default:
0.00Hz
b0-15
Lower limit of skip FREQ
band 2
Range: 0.00Hz ~ upper limit
frequency
Factory default:
0.00Hz
b0-16
Upper limit of skip FREQ
band 2
Range: 0.00Hz ~ upper limit
frequency
Factory default:
0.00Hz
b0-17
Lower limit of skip FREQ
band 3
Range: 0.00Hz ~ upper limit
frequency
Factory default:
0.00Hz
b0-18
Upper limit of skip FREQ
band 3
Range: 0.00Hz ~ upper limit
frequency
Factory default:
0.00Hz
Skip frequency is a function designed to prevent the drive run at resonance zone of mechanical
system. At most 3 skip zones can be defined. See Fig. 6-9.
Fig. 6-9
Once parameters of skip zones are set, the output frequency of the drive would automatically
get out of these skip zones even if the frequency setting is within these zones.
ATTENTION:
Output frequency of drive can normally pass through skip zones during Accel and Decel.
b0-19
Jog frequency
Range: 0.00Hz ~ upper limit
frequency
Factory default:
5.00Hz
This parameter sets the running frequency during jog. Jog Accel time is set by parameter b2-10
while its Decel time by parameter b2-11. Jog run command control could be performed through
调节后的频率
设定频率
b0-13
b0-14
b0-15
b0-16
b0-17
b0-18
跳跃频率
1
跳跃频率
2
跳跃频率
3
Frequency after adjustment
Skip frequency band 3
Skip frequency band 2
Skip frequency band 1
Frequency setting