GK600 User Manual
Chapter 5 List of Parameters
- 95 -
Parameter
Designation
Scope
Factory
default
Attr
E0-07
Mechanical brake open
current
0.0%~200.0%
120.0%
×
E0-08
Accel delay time after brake
open
0.0s~10.0s
1.0s
×
E0-09 Mechanical brake FREQ 0.00Hz~10.00Hz
2.00Hz
×
E0-10
Mechanical brake close
waiting time
0.0s~10.0s
0.0s
×
E0-11
Mechanical brake close
holding time
0.0s~10.0s
1.0s
×
Group E1 Protection Parameters
E1-00 Overvoltage stall
0: Prohibited
1: Allowed
1
×
E1-01
Overvoltage stall protection
voltage
120%~150%
130%
×
E1-02 Undervoltage stall
0: Disabled
1: Enabled
0
×
E1-03 Overload alarm
Ones place: detection option:
0: Always detect
1: Detect at constant speed only
Tens place: compared with:
0: Motor rated current
1: Drive rated current
Hundreds place: drive action
0: Alarm but run continued
1: Alarm and coast to stop
000
×
E1-04 Overload alarm threshold 20.0%~200.0%
130.0%
△
E1-05
Overload alarm activation
time
0.1s~60.0s
5.0s
△
E1-06 Protection action 1
Ones place: reserved
Tens place: action at IGBT
temperature measurement circuit
fault (OH3):
0: Coast to stop
1: Alarm but run continued
Hundreds place: abnormal EEPROM
(EPr) :
0: Coast to stop
1: Alarm but run continued
Thousands place: abnormal terminal
communication (TrC):
0: Coast to stop
1: Alarm but run continued
0000
×