Chapter 6 Specification of Parameters GK600 User Manual
- 160 -
2: Drive run preparation completed
The output of ON signal indicates that the drive is free of fault. Under this circumstance, the
drive is ready to accept run command.
3: Drive is running
The output is ON when the drive is running, and output is OFF when drive stopped.
4: Drive running at 0Hz (no output at stop)
When running at 0Hz, this corresponding terminal outputs ON signal. No ON signal will be
output at stop.
5: Drive running at 0Hz (output at stop)
Outputs ON signal when running at 0Hz, and also outputs ON signal at stop.
6: Run direction
Outputs OFF signal under forward run and outputs ON signal under reverse run.
7: Frequency attained
When the deviation of output frequency from set frequency is less than the value of C1-14
(Detective width of frequency attained), outputs ON.
8: Upper limit frequency attained
When output frequency attains b0-09 (upper limit frequency), outputs ON.
9: Lower limit frequency attained
When output frequency attains b0-10 (lower limit frequency), outputs ON.
10: Frequency detection FDT1
Terminal outputs ON signal when output frequency exceeds C1-10 (FDT1 upper bound)
and will not output OFF signal unless output frequency drops to below C1-11 (FDT1 lower
bound).
11: Frequency detection FDT2
Terminal outputs ON when output frequency exceeds C1-12 (FDT2 upper bound) and will
not output OFF unless output frequency drops to below C1-13 (FDT2 lower bound).
12: Reserved
13: Torque restricted
This takes effect only in the mode of sensor-less vector control. If output torque attains the
limit value of drive torque or brake torque, terminal outputs ON.
14: Fault output
When the drive is in fault, it outputs ON.
15: Alarm output
When inverter gives an alarm, ON signal is output.
16: Drive (motor) overloaded alarm
In case drive output current exceeds E1-04 (overload alarm threshold ) and its last time
exceeds E1-05 (overload alarm activated time that exceeding threshold), outputs ON. Refer
to parameters E1-03~E1-05 for information with regard to drive (motor) overloaded alarm.
ATTENTION: