GK600 User Manual Chapter 6 Specification of Parameters
-
217 -
F2-11
Setting of step 5
Range: 000~327
Factory default:
000
Ones place: frequency setting
0: Multi-step frequency 5 (F1-07)
1~7: same as F2-01
Tens place: run direction (same as F2-01)
Hundreds place: Accel/Decel time option (same as F2-01)
F2-12
Run time of step 5
Range: 0.0~6000.0s(min)
Factory default:
0.0s
Sets the run time of step 5 of simple PLC. The time unit is set by thousands place of F2-00.
F2-13
Setting of step 6
Range: 000~327
Factory default:
000
Ones place: frequency setting
0: Multi-step frequency 6 (F1-08)
1~7: same as F2-01
Tens place: run direction (same as F2-01)
Hundreds place: Accel/Decel time option (same as F2-01)
F2-14
Run time of step 6
Range: 0.0~6000.0s(min)
Factory default:
0.0s
Sets the run time of step 6 of simple PLC. The time unit is set by thousands place of F2-00.
F2-15
Setting of step 7
Range: 000~327
Factory default:
000
Ones place: frequency setting
0: Multi-step frequency 7 (F1-09)
1~7: same as F2-01
Tens place: run direction (same as F2-01)
Hundreds place: Accel/Decel time option (same as F2-01)
F2-16
Run time of step 7
Range: 0.0~6000.0s(min)
Factory default:
0.0s
Sets the run time of step 7 of simple PLC. The time unit is set by thousands place of F2-00.
F2-17
Setting of step 8
Range: 000~327
Factory default:
000