GK600 User Manual
Chapter 5 List of Parameters
- 97 -
Parameter
Designation
Scope
Factory
default
Attr
E1-13
Drive overheat alarm
threshold
0.0
℃
~100.0
℃
80.0
℃
△
Group F Application
Group F0 Process PID
F0-00 PID setting
0: F0-01 digital setting
1: AI1
2: AI2
3: EAI (on IO option)
4: X6/DI pulse input
5: Communication
0
×
F0-01 PID digital setting
0.0%~100.0%
50.0%
△
F0-02 PID feedback
0: AI1
1: AI2
2: EAI (on IO option)
3: AI1+AI2
4: AI1-AI2
5: Max {AI1, AI2}
6: Min {AI1, AI2}
7: X6/DI pulse input
8: Communication
0
×
F0-03 PID adjustment
Ones place: output FREQ
0: Must be the same direction as the
set run direction
1: Opposite direction allowed
Tens place: integration selection
0: Integral continued when FREQ
attains upper/lower limit
1: Integral stopped when FREQ
attains upper/lower limit
11
×
F0-04
PID positive and negative
adjustment
0: Positive adjustment
1: Negative adjustment
0
×
F0-05 Filtering time of PID setting 0.00s~60.00s
0.00s
△
F0-06
Filtering time of PID
feedback
0.00s~60.00s
0.00s
△
F0-07 Filtering time of PID output 0.00s~60.00s
0.00s
△
F0-08 Proportional gain Kp1
0.0~100.0
50.0
△
F0-09 Integration time Ti1
0.000s~50.000s
0.500s
△
F0-10 Derivative time Td1
0.000s~50.000s
0.000s
△
F0-11 Proportional gain Kp2
0.0~100.0
50.0
△
F0-12 Integration time Ti2
0.000s~50.000s
0.500s
△
F0-13 Derivative time Td2
0.000s~50.000s
0.000s
△