Chapter 6 Specification of Parameters
GK600 User Manual
- 232 -
Table 6-19
Tens place
Ones place
bit6
bit5
bit4
bit3
bit2
bit1
bit0
EX
X6
X5
X4
X3
X2
X1
0 means terminal input status is OFF, while 1 means terminal input status is ON.
For example:
If 23 (i.e. 0010 0011) is displayed at U0-18, it means the input status of terminals X1, X2 and X6
is ON and that of the other terminals is OFF.
If 05 (i.e. 0000 0101) is displayed at U0-18, it means the input status of terminals X1 and X3 is
ON while that of the other terminals is OFF.
U0-19
Digital output terminal
status
Range: 0~7
Factory default: 0
Corresponding relationship between digital output terminals and the bits of U0-19 is shown in Table
6-20:
Table 6-20
bit3
bit2
bit1
bit0
Option board relay
Control board relay
Y2
Y1
0 means terminal output status is OFF, while 1 means terminal output status is ON.
For example:
If 6 (i.e. 0110) is displayed at U0-19, it means the output status of terminals Y2 and control
board relay is ON while that of the other terminals is OFF.
U0-20 PID set
Range: 0.0%~100.0%
Factory default:
0.0%
U0-21 PID feedback
Range: 0.0%~100.0%
Factory default:
0.0%
U0-22 PID input offset
Range: -100.0%~100.0%
Factory default:
0.0%
U0-23 PLC step
Range: 0~15
Factory default: 0
U0-24 V/f separated target voltage Range: 0.0%~100.0%
Factory default:
0.0%
U0-25
V/f separated actual output
voltage
Range: 0.0%~100.0%
Factory default:
0.0%