GK600 User Manual
Chapter 6 Specification of Parameters
-
155 -
C0-16
Digital input terminal
enabled status setting 3
Range: 0000
~
1111
Factory default:
0000
This parameter sets the enabled condition of AI1, AI2 and EAI as digital input terminal (need to
be defined by C0-08~C0-10).
Ones place: AI1
0: Positive logic: < 3V, ON; > 7V, OFF
1: Negative logic: <3V, OFF; > 7V, ON
Tens place: AI2 (same as AI1)
Hundreds place: EAI (on IO option board; same as AI1)
Thousands place: reserved
C0-17
Terminal UP/DOWN frequency
adjustment action
Range: 0000~1111
Factory default:
0000
Ones place: at stop
0: Cleared
Terminal UP/DOWN frequency adjustment value is cleared when the drive stops.
1: Maintained
Terminal UP/DOWN frequency adjustment value is maintained when the drive stops.
Tens place: on power loss
0: Cleared
Terminal UP/DOWN frequency adjustment value is cleared in case of power loss.
1: Maintained
Terminal UP/DOWN frequency adjustment value is saved in case of power loss.
Hundreds place: integral function
0: No integral function
Adjustment step size is kept constant during terminal UP/DOWN adjustment, in compliance
with C0-18.
1: Integral function enabled
When frequency is adjusted through terminal UP/DOWN, initial step size is set by C0-18. With
the effective lasting time of the terminals, adjustment step size will increase gradually.
Thousands place: run direction
0: Changing run direction prohibited
When the frequency is decreased to 0Hz via terminal UP/DOWN, the drive will run at 0Hz and
won‟t change its run direction.
1: Changing run direction allowed
When the frequency is decreased to 0Hz via terminal UP/DOWN, the drive will change its run
direction if this decrease is continued.
C0-18
Terminal UP/DOWN frequency
change step size
Range:
0.00Hz/s~100.00Hz/s
Factory default:
0.03Hz/s