GK600 User Manual Chapter 6 Specification of Parameters
-
227 -
4: Emergency stop 1 (set Decel time by b2-09)
5: Emergency stop 2 (coast to stop)
6: Run command sources shifted (control panel/terminal/communication)
L0-01
Keys locked option
Range: 0~4
Factory default: 0
0: Not locked
1: All locked
2: Keys locked except RUN, STOP/RESET
3: Keys locked except STOP/RESET
4: Keys locked except >>
Please refer to Chapter 4 for locking operation of keys.
L0-02
Function of STOP key
Range: 0~1
Factory default: 0
0: STOP key active only at control panel control
1: STOP key deactivated under any command source
L0-03
Frequency adjustment through
keys
∧
/
∨
Range: 0000~1111
Factory default:
0100
Ones place: option at stop
0: Clear at stop
Keys
∧
/
∨
frequency adjustment step size is cleared at the stop of drive.
1: Holding at stop
Keys
∧
/
∨
frequency adjustment step size is held at the stop of drive.
Tens place: option at power loss
0: Clear at power loss
Keys
∧
/
∨
frequency adjustment step size is cleared at power loss.
1: Holding at power loss
Keys
∧
/
∨
frequency adjustment step size is saved at power loss.
Hundreds place: integrating option
0: Integrating disabled
Adjustment step size is kept constant when frequency is adjusted by keys
∧
/
∨
, and the
adjustment will be performed always with the step size set by L0-04.
1: Integrating enabled
When frequency is adjusted by keys
∧
/
∨
, the initial step size is the set value of L0-04. With
the press increase of
∧
/
∨
, adjustment step size shows cumulative integrating effect and
will increase gradually.
Thousands place: run direction
0: Direction changing prohibited
When the frequency is decreased to 0Hz by terminal UP/DOWN, the drive will run at 0Hz and
cannot be able to change the rotary direction.
1: Direction changing permitted