Chapter 7 Troubleshooting
GK600 User Manual
- 238 -
Fault
code
Fault
display
Fault description
Causes
Solutions
protection
overcurrent
overvoltage or overcurrent
Output short circuit
(phase-to-phase short
circuit or output ground
short circuit)
Check motor connection
and output ground
impedance
Loose connection of
control board
Pull out and reinsert the
cables of control board
Direct connection of
inverter module
Seek services
Control board
abnormal
Seek services
Switching power
supply failed
Seek services
8
tUN
Autotuning
failed
Bad motor connection
Check motor connection
Autotuning during
rotation of the motor
Autotuning in stationary
status of the motor
Big error between real
motor parameters and
the setting
Set the parameters
correctly according to
motor nameplate
9
oL1
Drive
overloaded
Torque boost is too big
under V/f control
Reduce torque boost
value
Start FREQ is too high Drop start frequency
Accel/Decel time is too
short
Prolong the Accel/Decel
time
Motor parameters are
improperly set
Set the parameters
correctly according to
motor nameplate
Output short circuit
(phase-to-phase short
circuit and output
ground short circuit)
Check motor connection
and output ground
impedance
Load is too heavy
Reduce the load
Inappropriate V/f curve
under V/f control
Set V/f curve correctly
Restart the rotary
motor
Reduce current limited
value or flying start