Chapter 5 List of Parameters GK600 User Manual
- 104 -
Parameter
Designation
Scope
Factory
default
Attr
F3-11
Action when the length
attained
0: Not stop
1: Stop
0
△
F3-12 Set count value
1~65535
1000
△
F3-13 Designated count value 1~65535
1000
△
Group H Communication Parameters
Group H0 MODBUS Communication Parameters
H0-00 SCI port selection
0: Local 485 port
1: Optional 232 port
0
×
H0-01
SCI port communication
configuration
Ones place: baud rate
0: 4800bps
1: 9600bps
2: 19200bps
3: 38400bps
4: 57600bps
5: 115200bps
Tens place: data format
0: 1-8-2-N format, RTU
1: 1-8-1-E format, RTU
2: 1-8-1-O Format, RTU
3: 1-7-2-N format, ASCII
4: 1-7-1-E format, ASCII
5: 1-7-1-O format, ASCII
Hundreds place: connection type
0: Direct cable connection (232/485)
1: MODEM (232)
Thousands place: communication
data handling at power loss
0: Saved at power loss
1: Not saved at power loss
0001
×
H0-02
Local address of SCI port
communication
0~247, 0 is broadcast address
1
×
H0-03
Time out detection of SCI
port communication
0.0s~1000.0s
0.0s
×
H0-04
Time delay of SCI port
communication
0ms~1000ms
0ms
×
H0-05 Master/Slave option
0: PC controls this drive
1: As master
2: As slave
0
×
H0-06
Parameter store address
when this drive working as
master
0:b0-02
1:F0-01
0
×