Chapter 3 Installation and Wiring GK600 User Manual
- 34 -
3.5 Terminal Configuration
Fig. 3-10 Terminal configuration
3.6 Main Circuit Terminals and Wiring
WARNING
Only qualified personnel familiar with AC motor drives are allowed to implement wiring.
Failure to comply may result in equipment damage and/or personnel injury even death.
Wiring should be in strict accordance with this manual, otherwise hazard of electric
shock or equipment damage exists.
Make sure input power supply has been completely disconnected before wiring
operation. Failure to comply will result in personnel injury even death.
All wiring operations and lines should comply with EMC and national and local industrial
safety regulations and/or electrical codes. The conductor diameter should be in
accordance with recommendations of this manual. Otherwise, hazard of equipment
damage, fire, and/or personnel injury exists.
Since leakage current of the drive may exceed 3.5mA, for safety's sake, the drive and
the motor must be grounded so as to avoid hazard of electric shock.
Be sure to perform wiring in strict accordance with the drive terminal marks. Never
connect three-phase power supply to output terminals U/T1, V/T2 and W/T3. Failure to
comply will result in equipment damage.
Only mount braking resistors at terminals and B2 when needed.
When needed, only mount DC reactors at terminals and , and remove the
jumper connected between and . Never connect the jumper and DC reactor to
other terminals since this will result in short circuit and equipment damage.
控制回路端子
主回路端子
接地端子
Control circuit terminals
Main circuit terminals
+ 2/B1
+ 1
+ 2
+ 1
+ 2
Grounding terminals