GK600 User Manual Chapter 6 Specification of Parameters
-
221 -
Fig. 6-55
a is the set Accel time (ramp up time), and d is the set Decel time (ramp down time).
F3-00
Wobble frequency function setting
Range: 0~1
Factory default: 0
0: Wobble frequency function disabled
1: Wobble frequency function enabled
F3-01
Wobble frequency run setting
Range: 0000~1111
Factory default:
0000
Ones place: started method
0: Automatically
Run at pre-frequency of wobble frequency set by F3-02, maintain Pre-frequency holding time
set by F3-03, and then automatically get into wobble frequency run.
1: Started by terminal
Digital input terminal "start wobble frequency" controls the run of wobble frequency. When
terminal inputs ON, the drive gets into wobble frequency run. When terminal inputs OFF, the
drive exits wobble frequency and runs at pre-frequency of wobble frequency. Under this
mode, Pre-frequency holding time is enabled.
Tens place: amplitude control
0: Relative to center frequency
Amplitude = F3-04 x current frequency setting.
1: Relative to maximum frequency
输出频率
时间
a
d
a
摆频预置
频率保持
时间
摆频周期
(F3-06)
三角波
上升时间
突跳频率
摆频频率上限
摆频频率下限
摆频中心频率
摆频预置频率
摆频正幅度
摆频负幅度
运行命令
停机命令
Output frequency
Wobble frequency
positive amplitude
Wobble frequency
negative amplitude
Hop frequency
Upper limit of wobble frequency
Center frequency
Lower limit of wobble frequency
Pre-wobble frequency
Pre- wobble
frequency
holding time
Triangular wave rise time
Wobble
frequency
cycle (F3-06)
Time
Run command
Stop command