GK600 User Manual
Chapter 6 Specification of Parameters
-
201 -
Thousands place: input supply fault /output phase loss (ISF, oPL)
0: Protection for neither input supply fault nor output phase loss
1: No protection for input supply fault, protection enabled for output phase loss
2: Protection enabled for input supply fault, no protection for output phase loss
3: Protection enabled both for input supply fault and output phase loss
ATTENTION:
Please set "protection action" with caution since inappropriate setting may extend the fault.
E1-08
Fault memory after power
loss
Range: 0~1
Factory default: 0
Determine whether or not the previous fault code is to be memorized and displayed upon the
power up of the drive after power loss.
0: Not memorized after power loss
1: Memorized after power loss
ATTENTION:
Undervoltage fault "LoU" is not memorized after power loss.
E1-09
Fault auto-reset times
Range: 0~20
Factory default: 0
E1-10
Auto-reset interval
Range: 2.0s~20.0s
Factory default:
2.0s
When a fault occurs during the running, the drive will run at 0Hz with the time set by E1-10, and
then the fault will be reset and the drive continues to run. Times of automatic reset is set by
E1-09. Automatic reset is prohibited and fault protection shall be executed immediately when
E1-09 is set to 0.
ATTENTION:
1) Automatic fault reset is not performed at the following types of faults:
Module protection "FAL"
Parameter identification failed "tUN"
Current detection abnormal "CtC"
Ground short circuit protection at output side "GdP"
Option board 1 connection abnormal "EC1"
Converter module overload protection "oL3"
Drive line connection abnormal "dLC"
Analog terminal functional mutex (TEr)
External equipment error "PEr"
Consecutive run time attained "to2"
Accumulative run time attained fault "to3"
Power supply abnormal during running "SUE"