F
Diagnostics and fault clearance
Festo – EMCA-EC-C-HP-EN – 2017-11e – English
399
Diagnostic messages and fault clearance
40h
Last teaching not successful
Definable as: -/
W
/I
Diagnostic memory: optional
Teaching of the current positioning record is not possible.
The current positioning record must be of the type 'position record'.
–
If parameterised as a warning: The warning disappears if the following TEACH attempt is success
ful or a switch takes place from the Teach mode (mode 1) to normal operation (mode 0).
41h
System reset
Definable as:
F
/-/-
Diagnostic memory: always
An internal firmware error has been detected.
Contact Festo repair service.
–
Resettable: Error can be reset immediately.
Definable error response(s): A
42h
Address Conflict Detection (ACD)
Definable as:
F
/-/-
Diagnostic memory: optional
There are at least two participants in the network with identical network configuration.
Correct network configuration (e.g. with FCT)
–
Resettable: Error can be reset immediately.
Definable error response(s): E
43h
FCT connection without master control
Definable as: -/
W
/I
Diagnostic memory: optional
There is no longer a connection to the FCT, e.g. the cable was disconnected.
Check the connection and perform a reset, if necessary.
–
For parameterisation as a warning: The warning disappears if the connection to the FCT is re-es
tablished.
44h
Parameter file not compatible with firmware
Definable as: -/
W
/I
Diagnostic memory: always
The parameter file that was just written to the device is not suitable for the firmware of that device.
As much data as possible is automatically taken over from the parameter file. Parameters that are
not initialised through the parameter file are imported from the default parameter file. If new firm
ware software is required, all parameters might not be written.
Load a valid parameter file into the device.
–
If parameterised as a warning: The warning disappears when a new parameter file is successfully
written.
47h
Modbus connection with master control
Definable as:
F
/-/-
Diagnostic memory: optional
The Modbus connection to the controller has been interrupted.
Check the connection and perform a reset.
–
Resettable: Error can be reset immediately.
Definable error reaction(s):
B
, C, D, E, F, G
–
For parameterisation as a warning: The warning disappears if the connection to the controller is
re-established.
Содержание EMCA-EC-67 CO Series
Страница 33: ...2 CANopen Festo EMCA EC C HP EN 2017 11e English 33 ...
Страница 73: ...3 EtherCAT with FHPP Festo EMCA EC C HP EN 2017 11e English 73 ...
Страница 87: ...4 EtherNet IP with FHPP Festo EMCA EC C HP EN 2017 11e English 87 ...
Страница 113: ...6 PROFINET IO with FHPP Festo EMCA EC C HP EN 2017 11e English 113 ...
Страница 116: ...7 FHPP 116 Festo EMCA EC C HP EN 2017 11e English ...
Страница 140: ...8 FHPP standard data I O data 140 Festo EMCA EC C HP EN 2017 11e English ...
Страница 148: ...9 Measuring reference system 148 Festo EMCA EC C HP EN 2017 11e English ...
Страница 210: ...10 Control via FHPP 210 Festo EMCA EC C HP EN 2017 11e English ...
Страница 223: ...11 Monitoring of the drive behaviour Festo EMCA EC C HP EN 2017 11e English 223 ...
Страница 367: ...D CANopen communication Festo EMCA EC C HP EN 2017 11e English 367 ...
Страница 402: ...F Diagnostics and fault clearance 402 Festo EMCA EC C HP EN 2017 11e English ...
Страница 413: ...EMCA EC 67 CO DIO EC EP PN Festo EMCA EC C HP EN 2017 11e English 413 ...
Страница 414: ...EMCA EC 67 CO DIO EC EP PN 414 Festo EMCA EC C HP EN 2017 11e English ...
Страница 415: ......