F
Diagnostics and fault clearance
390
Festo – EMCA-EC-C-HP-EN – 2017-11e – English
Diagnostic messages and fault clearance
14h
Negative direction locked
Definable as:
F
/-/-
Diagnostic memory: optional
A limit switch error or a software limit position error has occurred and subsequent positioning in the
blocked direction has been initiated.
Check target data.
Check positioning area.
This error can be reset immediately. Afterwards start a corresponding positioning record or move
the drive by using the jogging function. Movements in a negative direction are blocked.
–
Resettable: Error can be reset immediately.
Definable error response(s): A,
B
, C, E, F
15h
Output stage temperature exceeded
Definable as:
F
/-/-
Diagnostic memory: optional
The permissible limit value for the output stage temperature has been exceeded. The output stage is
possibly overloaded.
This error can only be acknowledged if the temperature is within the permissible range.
Check cylinder sizing.
Check the mechanics for sluggishness.
Reduce the ambient temperature, improve heat dissipation. Check ambient temperature. Con
sider power derating.
–
Resettable: Error can only be reset after the cause of the error has been eliminated.
Definable error response(s): A, B, C, D
16h
Output stage temperature too low
Definable as:
F
/-/-
Diagnostic memory: optional
The ambient temperature is below the permissible range.
Increase the ambient temperature. This error can only be acknowledged if the temperature is
within the permissible range.
–
Resettable: Error can only be reset after the cause of the error has been eliminated.
Definable error response(s): A, B, C, D
17h
Logic voltage exceeded
Definable as:
F
/-/-
Diagnostic memory: optional
The logic power supply monitor has detected an overvoltage. This is either due to an internal defect
or an excessive supply voltage.
Check external supply voltage directly on the device.
If the error is still present after a reset has been conducted, it means there is an internal defect
and the device has to be replaced.
–
Resettable: Error can only be reset after the cause of the error has been eliminated.
Definable error response(s): A,
B
Содержание EMCA-EC-67 CO Series
Страница 33: ...2 CANopen Festo EMCA EC C HP EN 2017 11e English 33 ...
Страница 73: ...3 EtherCAT with FHPP Festo EMCA EC C HP EN 2017 11e English 73 ...
Страница 87: ...4 EtherNet IP with FHPP Festo EMCA EC C HP EN 2017 11e English 87 ...
Страница 113: ...6 PROFINET IO with FHPP Festo EMCA EC C HP EN 2017 11e English 113 ...
Страница 116: ...7 FHPP 116 Festo EMCA EC C HP EN 2017 11e English ...
Страница 140: ...8 FHPP standard data I O data 140 Festo EMCA EC C HP EN 2017 11e English ...
Страница 148: ...9 Measuring reference system 148 Festo EMCA EC C HP EN 2017 11e English ...
Страница 210: ...10 Control via FHPP 210 Festo EMCA EC C HP EN 2017 11e English ...
Страница 223: ...11 Monitoring of the drive behaviour Festo EMCA EC C HP EN 2017 11e English 223 ...
Страница 367: ...D CANopen communication Festo EMCA EC C HP EN 2017 11e English 367 ...
Страница 402: ...F Diagnostics and fault clearance 402 Festo EMCA EC C HP EN 2017 11e English ...
Страница 413: ...EMCA EC 67 CO DIO EC EP PN Festo EMCA EC C HP EN 2017 11e English 413 ...
Страница 414: ...EMCA EC 67 CO DIO EC EP PN 414 Festo EMCA EC C HP EN 2017 11e English ...
Страница 415: ......