F
Diagnostics and fault clearance
Festo – EMCA-EC-C-HP-EN – 2017-11e – English
387
Diagnostic messages and fault clearance
07h
Limit switch positive
Definable as:
F
/-/-
Diagnostic memory: optional
The drive is at the positive limit switch.
Acknowledge error and move the drive in a negative direction to the permissible range. Also check
the movement range and record parameters, if necessary.
Check switches and cables.
Check positioning dynamics (overshoot?), e.g. with trace diagrams in FCT.
–
Resettable: Error can be reset immediately.
Definable error response(s): A,
B
, C, E, F
08h
Limit switch negative
Definable as:
F
/-/-
Diagnostic memory: optional
The drive is at the negative limit switch.
Reset error and move the drive in a positive direction into the permissible range. Also check the
movement range and record parameters, if necessary.
Check switches and cables.
Check positioning dynamics (overshoot?), e.g. with trace diagrams in FCT.
–
Resettable: Error can be reset immediately.
Definable error response(s): A,
B
, C, E, F
09h
Offset determination for current measurement
Definable as:
F
/-/-
Diagnostic memory: always
An error has occurred during initialisation of the current measurement.
Perform a software reset.
–
Resettable: Cannot be reset, software reset is necessary.
Definable error response(s): A
0Ah
General error
Definable as:
F
/-/-
Diagnostic memory: always
An internal error has occurred.
Restart device. If the error occurs frequently, contact Festo Service.
–
Resettable: Error can be reset immediately.
Parameterisable error response(s): B
0Bh
Parameter file invalid
Definable as:
F
/-/-
Diagnostic memory: always
No valid parameter set stored. After creation of the parameter file, a firmware update is performed, if
necessary: As much data as possible is automatically loaded from the parameter file. Parameters
that are not initialised by the parameter file are loaded from the default parameter file.
Check whether an error is present that can be reset first. Then, by saving the parameters in the
device, generate a new, valid parameter file or load a valid parameter record into the device. If the
error is still present, the hardware is perhaps defective.
–
Resettable: Error can be reset immediately.
Definable error response(s): A
Содержание EMCA-EC-67 CO Series
Страница 33: ...2 CANopen Festo EMCA EC C HP EN 2017 11e English 33 ...
Страница 73: ...3 EtherCAT with FHPP Festo EMCA EC C HP EN 2017 11e English 73 ...
Страница 87: ...4 EtherNet IP with FHPP Festo EMCA EC C HP EN 2017 11e English 87 ...
Страница 113: ...6 PROFINET IO with FHPP Festo EMCA EC C HP EN 2017 11e English 113 ...
Страница 116: ...7 FHPP 116 Festo EMCA EC C HP EN 2017 11e English ...
Страница 140: ...8 FHPP standard data I O data 140 Festo EMCA EC C HP EN 2017 11e English ...
Страница 148: ...9 Measuring reference system 148 Festo EMCA EC C HP EN 2017 11e English ...
Страница 210: ...10 Control via FHPP 210 Festo EMCA EC C HP EN 2017 11e English ...
Страница 223: ...11 Monitoring of the drive behaviour Festo EMCA EC C HP EN 2017 11e English 223 ...
Страница 367: ...D CANopen communication Festo EMCA EC C HP EN 2017 11e English 367 ...
Страница 402: ...F Diagnostics and fault clearance 402 Festo EMCA EC C HP EN 2017 11e English ...
Страница 413: ...EMCA EC 67 CO DIO EC EP PN Festo EMCA EC C HP EN 2017 11e English 413 ...
Страница 414: ...EMCA EC 67 CO DIO EC EP PN 414 Festo EMCA EC C HP EN 2017 11e English ...
Страница 415: ......