Diagnostics and fault clearance
398
Festo – EMCA-EC-C-HP-EN – 2017-11e – English
Diagnostic messages and fault clearance
37h
Standstill monitoring
Definable as: -/
W
/I
Diagnostic memory: optional
The actual position is outside the downtime window. Parameterisation of the window may be too
narrow.
Check parameterisation of the downtime window.
–
If parameterised as a warning: The warning disappears when the actual position is within the
standstill window again or a new record has been started.
38h
Parameter file access
Definable as:
F
/-/-
Diagnostic memory: optional
During a parameter file procedure all other reading and writing routines for the parameter file are
blocked.
Wait until the process is complete. The time between 2 parameter file downloads should not be
less than 3 s.
–
Acknowledgement option: Error can only be acknowledged after eliminating the cause.
Definable error response(s):
F
, G
39h
Trace warning
Definable as: -/
W
/-
Diagnostic memory: optional
An error has occurred during trace recording.
Start a new trace recording.
–
For parameterisation as a warning: The warning disappears if a new trace has been started.
3Dh
Start-up event
Definable as: -/-/-
Diagnostic memory: always
The device has been switched on or was switched on for longer than 48 days. This event also occurs
when deleting the diagnostic memory. The start-up event does not occur if the preceding entry in the
diagnostic memory has already been a start-up event.
This event is used only for better documentation of the diagnostic messages that occurred.
3Eh
Diagnostic memory
Definable as:
F
/-/-
Diagnostic memory: always
An error has occurred when writing or reading from the diagnostic memory.
Acknowledge error. If the error is still present, it means a memory module is probably defective or
an incorrect entry has been stored.
Clear diagnostic memory. If the error is still present, the device needs to be replaced.
–
Resettable: Error can be reset immediately.
Definable error response(s):
F
, G
3Fh
Record invalid
Definable as:
F
/-/-
Diagnostic memory: optional
The started record is invalid. The record data is implausible or the record type is invalid.
Check parameters of the record.
–
Resettable: Error can be reset immediately.
Definable error response(s): B, C, D,
E
, F, G
Содержание EMCA-EC-67 CO Series
Страница 33: ...2 CANopen Festo EMCA EC C HP EN 2017 11e English 33 ...
Страница 73: ...3 EtherCAT with FHPP Festo EMCA EC C HP EN 2017 11e English 73 ...
Страница 87: ...4 EtherNet IP with FHPP Festo EMCA EC C HP EN 2017 11e English 87 ...
Страница 113: ...6 PROFINET IO with FHPP Festo EMCA EC C HP EN 2017 11e English 113 ...
Страница 116: ...7 FHPP 116 Festo EMCA EC C HP EN 2017 11e English ...
Страница 140: ...8 FHPP standard data I O data 140 Festo EMCA EC C HP EN 2017 11e English ...
Страница 148: ...9 Measuring reference system 148 Festo EMCA EC C HP EN 2017 11e English ...
Страница 210: ...10 Control via FHPP 210 Festo EMCA EC C HP EN 2017 11e English ...
Страница 223: ...11 Monitoring of the drive behaviour Festo EMCA EC C HP EN 2017 11e English 223 ...
Страница 367: ...D CANopen communication Festo EMCA EC C HP EN 2017 11e English 367 ...
Страница 402: ...F Diagnostics and fault clearance 402 Festo EMCA EC C HP EN 2017 11e English ...
Страница 413: ...EMCA EC 67 CO DIO EC EP PN Festo EMCA EC C HP EN 2017 11e English 413 ...
Страница 414: ...EMCA EC 67 CO DIO EC EP PN 414 Festo EMCA EC C HP EN 2017 11e English ...
Страница 415: ......