100/180 mm PAPERLESS GRAPHIC RECORDER: USER GUIDE
HA028910
Issue 13 Sep 16
User Guide
Page 315
8.4.4 GROUP DATA (Cont.)
GROUP 6
Parameter
Description
Type
Access
Start Addr. Register
Name
Hex (Dec)
Length
See
table 8.3
for point types
Grp6 Trend type
Trend enhancements
Enum
Read only
B11F (45343) 1
0 = Interpolation enabled
1 = Adaptive recording enabled
Grp6 Trend rate
Trend update rate in milliseconds
Uint32
Read only B120 (45344)
2
Grp6 Archive rate
Archive (to fl ash) rate in milliseconds
Uint 32
Read only B122 (45346)
2
Grp6 Descriptor
Group descriptor (20 characters max.)
String_20
Read only B124 (45348)
10
Spare
B12E (45358)
10
Grp6 Channels in group 16 Registers holding the group contents, as follows:
(16)
Register 1
Uint16
Read only B138 (45368)
1
Bit 0: 0 = Point 1 not in group; 1 = Point 1 is in group
Bit 1: 0 = Point 2 not in group; 1 = Point 2 is in group
Bit 2: 0 = Point 3 not in group; 1 = Point 3 is in group
Etc.
Bit 15: 0 = Point 16 not in group; 1 = Point 16 is in group
Register 2 - as register 1, but for points 17 to 32
Uint16
Read only B139 (45369)
1
Register 3 - as register 1, but for points 33 to 48
Uint16
Read only B13A (45370)
1
Register 4 - as register 1, but for points 49 to 64
Uint16
Read only B13B (45371)
1
Register 5 - as register 1, but for points 65 to 80
Uint16
Read only B13C (45372)
1
Register 6 - as register 1, but for points 81 to 96
Uint16
Read only B13D (45373)
1
Register 7 - as register 1, but for points 97 to 112
Uint16
Read only B13E (45374)
1
Register 8 - as register 1, but for points 113 to 128
Uint16
Read only B13F (45375)
1
Register 9 - as register 1, but for points 129 to 144
Uint16
Read only B140 (45376)
1
Register 10 - as register 1, but for points 145 to 160
Uint16
Read only B141 (45377)
1
Register 11 - as register 1, but for points 161 to 176
Uint16
Read only B142 (45378)
1
Register 12 - as register 1, but for points 177 to 192
Uint16
Read only B143 (45379)
1
Register 13 - as register 1, but for points 193 to 208
Uint16
Read only B144 (45380)
1
Register 14 - as register 1, but for points 209 to 224
Uint16
Read only B145 (45381)
1
Register 15 - as register 1, but for points 225 to 240
Uint16
Read only B146 (45382)
1
Register 16 - as register 1, but for points 241 to 256
Uint16
Read only B147 (45383)
1
Grp6 Text length
Identifi es the length of a text message to be read
Uint16
Read/Write B148 (45384)
1
Grp6 Text time stamp
Time stamp of the text message to be read (UTC format) Double
Read only B149 (45385)
4
Grp6 Read text
Read text string from instrument display
String_60
Read only B14D (45389)
30
Reserved
B16B (45419)
30
Grp6 Write text
Write a text string to instrument display
String_60
Write only B189 (45449)
30
Reserved
B1A7 (45479)
30
Grp6 Batch start
Boolean Flag. Value 0001 starts new batch
Boolean
Write only B1C5 (45509)
1
Grp6 Batch stop
Boolean Flag. Value 0001 stops current batch
Boolean
Write only B1C6 (45510)
1
Grp6 Batch running
Batch status fl ag: 1 = Running; 0 = Not running
Boolean
Read only B1C7 (45511)
1
Grp6 Text fi eld 1
Batch fi eld 1 text string (max. 60 characters)
String_60
Read/Write B1C8 (45512)
30
Reserved
B1E6 (45542)
30
Grp6 Text fi eld 2
Batch fi eld 2 text string (max. 60 characters)
String_60
Read/Write B204 (45572)
30
Reserved
B222 (45602)
30
Grp6 Text fi eld 3
Batch fi eld 3 text string (max. 60 characters)
String_60
Read/Write B240 (45632)
30
Reserved
B25E (45662)
30
Grp6 Text fi eld 4
Batch fi eld 4 text string (max. 60 characters)
String_60
Read/Write B27C (45692)
30
Reserved
B29A (45722)
30
Grp6 Text fi eld 5
Batch fi eld 5 text string (max. 60 characters)
String_60
Read/Write B2B8 (45752)
30
Reserved
B2D6 (45782)
30
Grp6 Text fi eld 6
Batch fi eld 6 text string (max. 60 characters)
String_60
Read/Write B2F4 (45812)
30
Reserved
B312 (45842)
30
Spare
B330 (45872)
100