100/180 mm PAPERLESS GRAPHIC RECORDER: USER GUIDE
HA028910
Issue 13 Sep 16
User Guide
Page 296
Notes
1. For
maths
,
totalisers
and
counters
, see the relevant option description.
2. If an alarm’s Setpoint Source (
section 4.3.3
) is set to anything other than ‘Constant’ the value
returned will be the previously confi gured constant value.
8.4.2 CHANNEL CONFIGURATION DATA (Cont.)
CHANNEL 5
Parameter
Description
Type
Access
Start Addr. Register
Name
Hex (Dec)
Length
Ch5 Span high
Upper span value (display full scale)
Scaled
Read only 0303 (771)
1
Ch5 Span low
Lower span value (display ‘zero’)
Scaled
Read only 0304 (772)
1
Ch5 Zone high
Zone high value (two decimal places)
Scaled
Read only 0305 (773)
1
Ch5 Zone low
Zone low value (two decimal places)
Scaled
Read only 0306 (774)
1
Ch5 PV type
Input type
Enum
Read only 0307 (775)
1
1 = Analogue input
3 = Totaliser
2 = Maths
4 = Counter
Ch5 Decimal places
Number of decimal places (0 to 9)
Uint16
Read only 0308 (776)
1
(used by all scaled parameters except where stated)
Ch5 Colour
Channel colour (0 to 55) (See
Annex B
for RGB defi nitions)
Enum
Read only 0309 (777)
1
Ch5 Units
Units string (up to fi ve characters)
String_5
Read only 030A (778)
3
Spare
030D (781)
2
Ch5 Open string
Open Digital Input string (up to eight characters)
String_8
Read only 030F (783)
4
Spare
0313 (787)
4
Ch5 Close string
Closed Digital Input string (up to eight characters)
String_8
Read only 0317 (791)
4
Spare
031B (795)
4
Ch5 Descriptor
Channel descriptor (up to 20 characters)
String_20
Read only 031F (799)
10
Spare
0329 (809)
10
Ch5 No of alarms
Number of alarms on this channel (0 to 2)
Uint16
Read only 0333 (819)
1
Ch5 PV format
Enum
Read only 0334 (820)
1
0 = Numeric
1 = Digital strings
Spare
0335 (821)
60
Ch5 Alarm 1 enable
Alarm 1 enable
Enum
Read only 0371 (881)
1
0 = Off
2 = Latched
1 = Unlatched
3 = Trigger
Ch5 Alarm 1 type
Alarm 1 type
Enum
Read only 0372 (882)
1
0 = Absolute low
1 = Absolute high
2 = Deviation in
3 = Deviation out
4 = Rate of change rise
5 = Rate of change fall
Ch5 Alarm 1 setpoint
Trigger setpoint (Note 2)
Scaled
Read/Write 0373 (883)
1
Spare
0374 (884)
10
Ch5 Alarm 2 enable
Alarm 2 enable (As alarm 1 enable, above)
Enum
Read only 037E (894)
1
Ch5 Alarm 2 type
Alarm 2 type (As alarm 1 type, above)
Enum
Read only 037F (895)
1
Ch5 Alarm 2 setpoint
Trigger setpoint (Note 2)
Scaled
Read/Write 0380 (896)
1
Spare
0381 (897)
10
Ch5 Alarm 3 enable
Alarm 3 enable (As alarm 1 enable above)
Enum
Read only 02E9 (907)
1
Ch5 Alarm 3 type
Alarm 3 type (As alarm 1 type above)
Enum
Read only 02EA (908)
1
Ch5 Alarm 3 setpoint
Trigger setpoint (Note 2)
Scaled
Read/Write 02EB (909)
1
Spare
02EC (910)
10
Ch5 Alarm 4 enable
Alarm 4 enable (As alarm 1 enable above)
Enum
Read only 02F6 (920)
1
Ch5 Alarm 4 type
Alarm 4 type (As alarm 1 type above)
Enum
Read only 02F7 (921)
1
Ch5 Alarm 4 setpoint
Trigger setpoint (Note 2)
Scaled
Read/Write 02F8 (922)
1
Spare
02F9 (923)
10