100/180 mm PAPERLESS GRAPHIC RECORDER: USER GUIDE
HA028910
Issue 13 Sep 16
User Guide
Page 297
8.4.2 CHANNEL CONFIGURATION DATA (Cont.)
CHANNEL 6
Notes
1. For
maths
,
totalisers
and
counters
, see the relevant option description.
2. If an alarm’s Setpoint Source (
section 4.3.3
) is set to anything other than ‘Constant’ the value
returned will be the previously confi gured constant value.
Parameter
Description
Type
Access
Start Addr. Register
Name
Hex (Dec)
Length
Ch6 Span high
Upper span value (display full scale)
Scaled
Read only 03A5 (933)
1
Ch6 Span low
Lower span value (display ‘zero’)
Scaled
Read only 03A6 (934)
1
Ch6 Zone high
Zone high value (two decimal places)
Scaled
Read only 03A7 (935)
1
Ch6 Zone low
Zone low value (two decimal places)
Scaled
Read only 03A8 (936)
1
Ch6 PV type
Input type
Enum
Read only 03A9 (937)
1
1 = Analogue input
3 = Totaliser
2 = Maths
4 = Counter
Ch6 Decimal places
Number of decimal places (0 to 9)
Uint16
Read only 03AA (938)
1
(used by all scaled parameters except where stated)
Ch6 Colour
Channel colour (0 to 55) (See
Annex B
for RGB defi nitions)
Enum
Read only 03AB (939)
1
Ch6 Units
Units string (up to fi ve characters)
String_5
Read only 03AC (940)
3
Spare
03AF (943)
2
Ch6 Open string
Open Digital Input string (up to eight characters)
String_8
Read only 03B1 (945)
4
Spare
03B5 (949)
4
Ch6 Close string
Closed Digital Input string (up to eight characters)
String_8
Read only 03B9 (953)
4
Spare
03BD (957)
4
Ch6 Descriptor
Channel descriptor (up to 20 characters)
String_20
Read only 03C1 (961)
10
Spare
03CB (971)
10
Ch6 No of alarms
Number of alarms on this channel (0 to 2)
Uint16
Read only 03D5 (981)
1
Ch6 PV format
Enum
Read only 03D6 (982)
1
0 = Numeric
1 = Digital strings
Spare
03D7 (983)
60
Ch6 Alarm 1 enable
Alarm 1 enable
Enum
Read only 0413 (1043)
1
0 = Off
2 = Latched
1 = Unlatched
3 = Trigger
Ch6 Alarm 1 type
Alarm 1 type
Enum
Read only 0414 (1044)
1
0 = Absolute low
1 = Absolute high
2 = Deviation in
3 = Deviation out
4 = Rate of change rise
5 = Rate of change fall
Ch6 Alarm 1 setpoint
Trigger setpoint (Note 2)
Scaled
Read/Write 0415 (1045)
1
Spare
0416 (1046)
10
Ch6 Alarm 2 enable
Alarm 2 enable (As alarm 1 enable, above)
Enum
Read only 0420 (1056)
1
Ch6 Alarm 2 type
Alarm 2 type (As alarm 1 type, above)
Enum
Read only 0421 (1057)
1
Ch6 Alarm 2 setpoint
Trigger setpoint (Note 2)
Scaled
Read/Write 0422 (1058)
1
Spare
0423 (1059)
10
Ch6 Alarm 3 enable
Alarm 3 enable (As alarm 1 enable above)
Enum
Read only 042D (1069)
1
Ch6 Alarm 3 type
Alarm 3 type (As alarm 1 type above)
Enum
Read only 042E (1070)
1
Ch6 Alarm 3 setpoint
Trigger setpoint (Note 2)
Scaled
Read/Write 042F (1071)
1
Spare
0430 (1072)
10
Ch6 Alarm 4 enable
Alarm 4 enable (As alarm 1 enable above)
Enum
Read only 043A (1082)
1
Ch6 Alarm 4 type
Alarm 4 type (As alarm 1 type above)
Enum
Read only 043B (1083)
1
Ch6 Alarm 4 setpoint
Trigger setpoint (Note 2)
Scaled
Read/Write 043C (1084)
1
Spare
043D (1085)
10