100/180 mm PAPERLESS GRAPHIC RECORDER: USER GUIDE
HA028910
Issue 13 Sep 16
User Guide
Page 142
4.3.12 (Cont.) TOTALISER MODBUS ADDRESSING
IEEE AREA TOTALISER RUN-TIME DATA
The following table gives addresses for the specifi ed 32-bit fl oating-point values, for totaliser 1. Gener-
ally, Parameter address for totaliser N = Parameter address for totaliser 1 + 4(N-1) (decimal).
TOTALISER 1
Parameter
Description
Type
Access
Start Addr.
Register
Name
Hex (Dec)
Length
Totaliser 1 value
Current process value (PV)
Float
Read/Write FB7F (64383)
2
Totaliser 1 status
Channel status
Enum
Read only
FB81 (64385)
1
0 = Good PV
5 = Ranging error
1 = Channel off
6 = Overfl ow
2 = Over range
7 = Bad PV
3 = Under range
8 = No data
4 = Hardware error
Totaliser 1 Alarms
Alarm information
Uint16
-
FB82 (64386)
1
Bit 0: 0 = Alarm 1 inactive; 1 = Alarm 1 active
Read only
Bit 1: 0 = No alarm 1 Ack. required; 1 = Ack. required
Read only
Bit 2: 1 = Acknowledge alarm 1
Read/Write
Bit 3: Spare
Bit 4: 0 = Alarm 2 inactive; 1 = Alarm 2 active
Read only
Bit 5: 0 = No Alarm 2 Ack. required; 1 = Ack. required
Read only
Bit 6: 1 = Acknowledge alarm 2
Read/Write
Bit 7: Spare
Bit 8: 0 = Alarm 3 inactive; 1 = Alarm 3 active
Read only
Bit 9: 0 = No alarm 3 Ack. required; 1 = Ack. required
Read only
Bit 10: 1 = Acknowledge alarm 3
Read/Write
Bit 11: Spare
Bit 12: 0 = Alarm 4 inactive; 1 = Alarm 4 active
Read only
Bit 13: 0 = No Alarm 4 Ack. required; 1 = Ack. required
Read only
Bit 14: 1 = Acknowledge alarm 4
Read/Write
Bit 15: Spare