100/180 mm PAPERLESS GRAPHIC RECORDER: USER GUIDE
HA028910
Issue 13 Sep 16
User Guide
Page 301
8.4.2 CHANNEL CONFIGURATION DATA (Cont.)
CHANNEL 10
Notes
1. For
maths
,
totalisers
and
counters
, see the relevant option description.
2. If an alarm’s Setpoint Source (
section 4.3.3
) is set to anything other than ‘Constant’ the value
returned will be the previously confi gured constant value.
Parameter
Description
Type
Access
Start Addr. Register
Name
Hex (Dec)
Length
Ch10 Span high
Upper span value (display full scale)
Scaled
Read only 062D (1581)
1
Ch10 Span low
Lower span value (display ‘zero’)
Scaled
Read only 062E (1582)
1
Ch10 Zone high
Zone high value (two decimal places)
Scaled
Read only 062F (1583)
1
Ch10 Zone low
Zone low value (two decimal places)
Scaled
Read only 0630 (1584)
1
Ch10 PV type
Input type
Enum
Read only 0631 (1585)
1
1 = Analogue input
3 = Totaliser
2 = Maths
4 = Counter
Ch10 Decimal places
Number of decimal places (0 to 9)
Uint16
Read only 0632 (1586)
1
(used by all scaled parameters except where stated)
Ch10 Colour
Channel colour (0 to 55) (See
Annex B
for RGB defi nitions)
Enum
Read only 0633 (1587)
1
Ch10 Units
Units string (up to fi ve characters)
String_5
Read only 0634 (1588)
3
Spare
0637 (1591)
2
Ch10 Open string
Open Digital Input string (up to eight characters)
String_8
Read only 0639 (1593)
4
Spare
063D (1597)
4
Ch10 Close string
Closed Digital Input string (up to eight characters)
String_8
Read only 0641 (1601)
4
Spare
0645 (1605)
4
Ch10 Descriptor
Channel descriptor (up to 20 characters)
String_20
Read only 0649 (1609)
10
Spare
0653 (1619)
10
Ch10 No of alarms
Number of alarms on this channel (0 to 2)
Uint16
Read only 065D (1629)
1
Ch10 PV format
Enum
Read only 065E (1630)
1
0 = Numeric
1 = Digital strings
Spare
065F (1631)
60
Ch10 Alarm 1 enable
Alarm 1 enable
Enum
Read only 069B (1691)
1
0 = Off
2 = Latched
1 = Unlatched
3 = Trigger
Ch10 Alarm 1 type
Alarm 1 type
Enum
Read only 069C (1692)
1
0 = Absolute low
1 = Absolute high
2 = Deviation in
3 = Deviation out
4 = Rate of change rise
5 = Rate of change fall
Ch10 Alarm 1 setpoint
Trigger setpoint (Note 2)
Scaled
Read/Write 069D (1693)
1
Spare
069E (1694)
10
Ch10 Alarm 2 enable
Alarm 2 enable (As alarm 1 enable, above)
Enum
Read only 06A8 (1704)
1
Ch10 Alarm 2 type
Alarm 2 type (As alarm 1 type, above)
Enum
Read only 06A9 (1705)
1
Ch10 Alarm 2 setpoint
Trigger setpoint (Note 2)
Scaled
Read/Write 06AA (1706)
1
Spare
06AB (1707)
10
Ch10 Alarm 3 enable
Alarm 3 enable (As alarm 1 enable above)
Enum
Read only 06B5(1717)
1
Ch10 Alarm 3 type
Alarm 3 type (As alarm 1 type above)
Enum
Read only 06B6(1718)
1
Ch10 Alarm 3 setpoint
Trigger setpoint (Note 2)
Scaled
Read/Write 06B7 (1719)
1
Spare
06B8 (1720)
10
Ch10 Alarm 4 enable
Alarm 4 enable (As alarm 1 enable above)
Enum
Read only 06C2 (1730)
1
Ch10 Alarm 4 type
Alarm 4 type (As alarm 1 type above)
Enum
Read only 06C3 (1731)
1
Ch10 Alarm 4 setpoint
Trigger setpoint (Note 2)
Scaled
Read/Write 06C4 (1732)
1
Spare
06C5 (1733)