100/180 mm PAPERLESS GRAPHIC RECORDER: USER GUIDE
HA028910
Issue 13 Sep 16
User Guide
Page 314
8.4.4 GROUP DATA (Cont.)
GROUP 5
Parameter
Description
Type
Access
Start Addr. Register
Name
Hex (Dec)
Length
See
table 8.3
for point types
Grp5 Trend type
Trend enhancements
Enum
Read only
AEAA (44714)
1
0 = Interpolation enabled
1 = Adaptive recording enabled
Grp5 Trend rate
Trend update rate in milliseconds
Uint32
Read only AEAB (44715)
2
Grp5 Archive rate
Archive (to fl ash) rate in milliseconds
Uint 32
Read only AEAD (44717)
2
Grp5 Descriptor
Group descriptor (20 characters max.)
String_20
Read only AEAF (44719)
10
Spare
AEB9 (44729)
10
Grp5 Channels in group 16 Registers holding the group contents, as follows:
(16)
Register 1
Uint16
Read only AEC3 (44739)
1
Bit 0: 0 = Point 1 not in group; 1 = Point 1 is in group
Bit 1: 0 = Point 2 not in group; 1 = Point 2 is in group
Bit 2: 0 = Point 3 not in group; 1 = Point 3 is in group
Etc.
Bit 15: 0 = Point 16 not in group; 1 = Point 16 is in group
Register 2 - as register 1, but for points 17 to 32
Uint16
Read only AEC4 (44740)
1
Register 3 - as register 1, but for points 33 to 48
Uint16
Read only AEC5 (44741)
1
Register 4 - as register 1, but for points 49 to 64
Uint16
Read only AEC6 (44742)
1
Register 5 - as register 1, but for points 65 to 80
Uint16
Read only AEC7 (44743)
1
Register 6 - as register 1, but for points 81 to 96
Uint16
Read only AEC8 (44744)
1
Register 7 - as register 1, but for points 97 to 112
Uint16
Read only AEC9 (44745)
1
Register 8 - as register 1, but for points 113 to 128
Uint16
Read only AECA (44746)
1
Register 9 - as register 1, but for points 129 to 144
Uint16
Read only AECB (44747)
1
Register 10 - as register 1, but for points 145 to 160
Uint16
Read only AECC (44748)
1
Register 11 - as register 1, but for points 161 to 176
Uint16
Read only AECD (44749)
1
Register 12 - as register 1, but for points 177 to 192
Uint16
Read only AECE (44750)
1
Register 13 - as register 1, but for points 193 to 208
Uint16
Read only AECF (44751)
1
Register 14 - as register 1, but for points 209 to 224
Uint16
Read only AED0 (44752)
1
Register 15 - as register 1, but for points 225 to 240
Uint16
Read only AED1 (42253)
1
Register 16 - as register 1, but for points 241 to 256
Uint16
Read only AED2 (44754)
1
Grp5 Text length
Identifi es the length of a text message to be read
Uint16
Read/Write AED3 (44755)
1
Grp5 Text time stamp
Time stamp of the text message to be read (UTC format) Double
Read only AED4 (44756)
4
Grp5 Read text
Read text string from instrument display
String_60
Read only AED8 (44760)
30
Reserved
AEF6 (44790)
30
Grp5 Write text
Write a text string to instrument display
String_60
Write only AF14 (44820)
30
Reserved
AF32 (44850)
30
Grp5 Batch start
Boolean Flag. Value 0001 starts new batch
Boolean
Write only AF50 (44880)
1
Grp5 Batch stop
Boolean Flag. Value 0001 stops current batch
Boolean
Write only AF51 (44881)
1
Grp5 Batch running
Batch status fl ag: 1 = Running; 0 = Not running
Boolean
Read only AF52 (44882)
1
Grp5 Text fi eld 1
Batch fi eld 1 text string (max. 60 characters)
String_60
Read/Write AF53 (44883)
30
Reserved
AF71 (44913)
30
Grp5 Text fi eld 2
Batch fi eld 2 text string (max. 60 characters)
String_60
Read/Write AF8F (44943)
30
Reserved
AFAD (44973)
30
Grp5 Text fi eld 3
Batch fi eld 3 text string (max. 60 characters)
String_60
Read/Write AFCB (45003)
30
Reserved
AFE9 (45033)
30
Grp5 Text fi eld 4
Batch fi eld 4 text string (max. 60 characters)
String_60
Read/Write B007 (45063)
30
Reserved
B025 (45093)
30
Grp5 Text fi eld 5
Batch fi eld 5 text string (max. 60 characters)
String_60
Read/Write B043 (45123)
30
Reserved
B061 (45153)
30
Grp5 Text fi eld 6
Batch fi eld 6 text string (max. 60 characters)
String_60
Read/Write B08F (45183)
30
Reserved
B09D (45213)
30
Spare
B0BB (45243)
100