TECHNICAL SPECIFICATION (RECORDER) (Cont.)
Ethernet Communications
Type
10/100 base T (IEEE802.3)
Protocols
TCP/IP, FTP, DHCP, BootP, SNTP, Modbus, SMTP, ICMP.
Cable
Type:
CAT5
Maximum length:
100 metres
Termination:
RJ45
RJ45 LED indicators
Green:
Indicates a 100MB link
Yellow:
Indicates Ethernet activity
Internal green LED
Indicates a 10MB link
Serial communications option
Number of ports
Two, at rear of instrument
Protocol
ASCII input, ASCII printer, Modbus master, Modbus slave.
Transmission standards
EIA232 and/or EIA485, software selectable per port. EIA485 can be connected as 3-wire or 5-wire as required.
Isolation (dc to 65Hz BS EN61010)
Installation category II; Pollution degree 2.
Terminals to ground:
50 V RMS or dc (basic insulation)
Transmitter power supply (Isolated) (Small frame recorders only )
Number of outputs
Three
Output voltage
25V nominal
Max. current
20mA per output
Isolation (dc to 65Hz BS EN61010)
Installation category II; Pollution degree 2.
Channel to channel:
100V RMS or dc (double insulation)
Channel to ground:
100V RMS or dc (basic insulation).
Fuse (20mm Type T)
Supply voltage = 110/120Vac:
100 mA
Supply voltage = 220/240Vac:
63 mA
USB ports
Number of ports
1 at front of recorder (standard*); 2 further ports (optional - at rear of instrument)
(*No front USB port with Stainless steel case option)
Standard
USB1.1
Transmission speeds
12Mbits/sec (full speed devices) or 1.5Mbits/sec (low speed devices)
Maximum current per port
500mA
Peripherals supported
Floppy disk drive, Keyboard, Bar code reader, Mouse, Memory stick.
Note: The recorder meets the industrial EMC requirements of BS EN61326. Typically, USB pe-
ripherals are tested to domestic information technology standards (BS EN55022) with category C
performance. Some USB peripherals, designed for use in domestic or offi ce environments, can be
susceptible to
‘lock up’ in environments containing high electromagnetic fi eld strengths. In order
to recover from such ‘lock up’ situations, the peripheral must be disconnected and then recon-
nected. Recorder operation is not affected.
Other items
Virus susceptibility
The 6000 series VxWorks operating system is immune to viruses targeted at Windows based operating systems.
As at December 2005, there are no known viruses that target VxWorks.
Calibration coeffi cients
Input:
The Read-only input coeffi cients are stored in EEPROM on the input board.
Instrument:
Instrument confi guration is held in FLASH memory and has no effect on calibration coeffi cients.