100/180 mm PAPERLESS GRAPHIC RECORDER: USER GUIDE
HA028910
Issue 13 Sep 16
User Guide
Page 377
15.3 CHART MESSAGES
If Audit Trail is enabled then a number of messages appear on the chart, and included in the history fi le
as described in section 4.4.2. If the TUS option is enabled, ‘Pre calibration’ and/or ‘Post calibration tick
boxes are ticked, then further messages are produced for each adjusted channel, showing the pre cali-
bration and post calibration high and low values.
Example:
05/10/10 16:20:57 5) Temps1e Pre cal high 5.010 Post cal high 5.000
05/10/10 16:20:57 4) Temps1d Pre cal high 4.994 Post cal high 5.000
05/10/10 16:20:57 3) Temps1c Pre cal high 5.001 Post cal high 5.000
05/10/10 16:20:57 2) Temps1b Pre cal high 4.997 Post cal high 5.000
05/10/10 16:20:57 1) Temps1a Pre cal high 4.993 Post cal high 5.000
05/10/10 16:20:57 5) Temps1e Pre cal low 0.000 Post cal low 0.000
05/10/10 16:20:57 4) Temps1e Pre cal low -0.002 Post cal low 0.000
05/10/10 16:20:57 3) Temps1e Pre cal low -0.002 Post cal low 0.000
05/10/10 16:20:57 2) Temps1e Pre cal low 0.001 Post cal low 0.000
05/10/10 16:20:57 1) Temps1e Pre cal low -0.003 Post cal low 0.000
15.4 OTHER ITEMS
Input channels 6, 12, 18 etc. are reference channels used to measure the temperature of the remote CJ
block. They are therefore excluded from the adjust procedure and channel offsets (
section 4.3.3
) cannot
be applied to them.
In ‘Save and Restore’, channel confi guration will not be restored.
Batch initiation must be by operator action - job triggered batches do not support pre and post calibra-
tion.