100/180 mm PAPERLESS GRAPHIC RECORDER: USER GUIDE
User Guide
Page 223
HA028910
Issue 13 Sep 16
4.6.4 INPUT ADJUST (Cont.)
ADJUST PROCEDURE
Operation of the Adjust Channels key calls the low-end adjust page, as shown in fi gure 4.6.4b.
Figure 4.6.4b Typical low-end input adjust page
Fast Settle
Reduces the time taken for the readings to stabilise.
Low Point
Usually 0, but a different value can be entered here, if required.
Apply the Low point value to the relevant input channels, and wait for the recorder readings to become
stable. When the readings are stable, press the Apply key, to call the High-end page depicted in fi gure
4.6.4c, below.
Figure 4.6.4c Typical high-end input adjust page
Fast Settle
Reduces the time taken for the readings to stabilise.
High Point
Default value displayed, but a different value can be entered here, if required.
Apply the High point value to the relevant input channels, and wait some minutes for the recorder read-
ings to become stable. When the readings are stable, press the Apply key, to return to the status page.
Note: Adjusting a channel invalidates the accuracy values given in the specifi cation in
Annex A
for
that channel.
Specify the sensor low point and connect the
c o r r e s p o n d i n g i n p u t .
2) Channel 2
3) Channel 3
4) Channel 4
-0.0002
6) Channel 6
-0.0002
-0.0001
-0.0026
0.0000
1) Channel 1
Low Point
0
When the values below have settled select
Apply.
Unadjusted
Unadjusted
Unadjusted
Unadjusted
Unadjusted
Apply
Discard
Fast settle
Specify the sensor high point and connect the
corresponding input.
2) Channel 2
3) Channel 3
4) Channel 4
4.9994
6) Channel 6
5.0010
4.9972
4.9993
5.0110
1) Channel 1
High Point
5
When the values below have settled select
Apply.
Unadjusted
Unadjusted
Unadjusted
Unadjusted
Unadjusted
Apply
Discard
Fast settle