Relay contacts
Galvanic isolation
At the same potential are:
•
Current output 1 and the power supply
•
Current output 2 and the CPC 30.
The remaining circuits are galvanically isolated from each other.
Derivative action time T
v
0.0 … 999.9 min
With the maximum settable frequency in PFM
120 min
-1
With the maximum settable period length in PWM
1 ... 999.9 s
With PWM minimum switch-on period
0.4 s
The NC/NO contact type can be set by software.
Switching voltage
Max. 250 V AC / 125 V DC
Switching current
Max. 3 A
Switching power
Max. 750 VA
Lifespan
≥
5 million switching cycles
CPG 30:
Digital outputs
Optoelectronic coupler, max. switching voltage
30 V
Max. switching current
100 mA
Max. switching power
3 W
Control for external valve
"
Caution!
Device damage possible
. A separate fuse must be provided at the output.
Switched power supply.
Max. switching current
I
max
= 3 A
Max. switching power
P
max
= 750 VA
Fig. 38: Switched power supply to control the external additional valve
41
42
N/L–
L/L+
C07-CPC30xxx-04-12-00-en-004
external valve
(optional)