TopClean S CPC 30
6 Commissioning
Hauser
57
Configuring the CPM 153
Please configure the relays in the following order:
1.
Actuators
2.
Characteristic curve:
In the user settings (see below) you switch directly to a controller simulation and can
check the settings made and change them if necessary.
CODE
CHOICE
(default = bold)
INFO
(E1, 2 = Editor types, s. page 28)
User
settings
M1
Off
On
Select controller functions
!
Note!
You must activate the controller functions
after
you
have configured the controller in this menu branch.
M2
Batch one-sided
Inline one-sided
Batch two-sided
Inline two-sided
Select the process type
which describes your process.
One-sided
: control using either acid
or
alkali
Two-sided
: control using acid
and
alkali. You can only
select this function if you have defined two controllers
(in the "Contacts" menu and/or via the current output).
E1
M3
Actuators
Characteristic curve
Select external hardware
For correct operation, you must completely configure
these four submenus.
Actuators
: here, you can select and configure the
methods which the controller uses to output the
actuating variable.
Characteristic curve
: here, you enter the controller
parameters (neutral zone, set point, etc.). With this
selection, you can also reach the "active measuring
menu" (see Field 196).
E1
Actuators:
With selection "one-sided" in Field M1:
MA1
Acid
Alkali
Dosing
Select the medium to be dosed to the process.
E1
MA2
Pulse length
Pulse frequency
3-point step controller
Current output
Select control type
E1
MA3
+Relay
–Relay
Motor run time
n.c.
n.c.
Relay selection
(for three-point step controller)
+Relay
: Open the valve further (= increase dosing)
Relay
: Close the valve further (= reduce dosing)
Option n.c. (= not connected). After this, those relays
which are released in the Contacts menu are always
offered as the default.
Motor run time
: The time the motor drive requires to
move the valve from completely closed to completely
open. The CPM 153 requires this to be able to calculate
the required pick-up time of the relay for any required
position change.
!
Note!
If you cannot select a relay here, use the "Contacts"
menu to make relays available for the controller
function.