11 Appendix
TopClean S CPC 30
126
EHauser
PARAM
Set controller hold
Freeze variables
Yes
No (controllers
n/a with hold)
Alarm for maximum
dosing time
60 s
Selection
On-site calibration
Special buffer
(only pH)
General settings
Calibration timer
Calibration
(only pH)
MTC
ATC 1
ATC 2
Slope channel 1
(only pH)
45.00mV/pH
(5.00...57.00mV/pH)
Slope channel 2
(only pH)
45.00mV/pH
(5.00...57.00mV/pH
Zero point channel 1
07.00 pH/0100mV
(0.00...14.00pH
1...1500mV))
Zero point channel 2
07.00 pH/0100mV
(0.00...14.00pH
1...1500mV))
Cal timer
Cal timer
Warning in
Remaining
time
on
0001h
0001:00
Select hold current
last
fixed
Min (2,4mA)
Max (22mA)
Hold current
(only test)
(0...100%)
000%
Set hold after-effect
time
000s
(0...999s)
C07-CPC30xxx-19-06-08-de-008.EPS
Delta alarm
Function off
Main-
tenance 1.00pH
Function 3.00pH
Assignment to each
error number:
Error no. /
Relay assignment /
Alarm error current /
Cleaning trigger /
Isotherm. comp.
Channel
(only pH)
1
Off
On
Back to return
field
Back to return
field
Selection
Alarm
Hold
Calibration
Measured variable,
display, bus configura-
tion,current output,
contacts, temperature,
see above)
Auto hold with
:
Cal.
off
Diag.
off
Param off
Enter alarm delay
0000min
(0...2000min)
Warning, if "Min"
and current range
0...20 mA are
selected
Select
error current
Min (2,4mA)
Max (22mA)
Off
"Return field"
Press the PARAM key
to return to these
highlighted fields
=
Code entry required
PARAM
Special functions
Manual Operation
Quick Setup
Basic Settings
Special buffer
Edit table for
Buffer no.
1
(1...3)
Special buffer
Enter number of
support points
02
(2...10)
Special buffer: Table
status info field
Invalid table
--> back
valid table
--> back
Back to special
buffer
Edit table... or
Use Param to return
to return field
Cal parameters
(only pH)
Data entry
Manual buffer
Fixed buffer
Automatic buffer
recognition
Cal parameters
(only redox abs.)
Data entry abs.
Calibration abs.
Cal parameters
(only redox %)
Data entry abs.
Data entry rel.
Data entry abs.
Data entry rel.
Buffer type
(only pH, fixed
buffer, auto buffer)
DIN
E+H
....
Special buffer
Buffer 1
(only pH)
Buffer
Buffer
Buffer
2.0
4.01
6.98
....
Buffer
(only pH)
Buffer
Buffer
Buffer
2
4.01
6.98
9.18
....
Back to return
field
Isotherm. Intersec-
tion point
(only pH)
07.00pH
(-2...16pH)
Special buffer
Enter support points
°C pH
000.00 00.00
Query
Table ok
Delete elements
(then back to the
support points)