SiAUY361411EA
Flow Charts for Troubleshooting
Troubleshooting
168
44
Indoor Unit and Remote Control Mismatch
Error
code
UA
Description
of the failure
Sub-code 2: The number of connected remote control units does not match the number of supported remote
control units specific to the model.
Sub-code 5: Unable to receive signals from the ignition CPU when the power is turned ON.
Possible
causes
of the failure
CPU mismatch; indoor/outdoor unit connection failure; communication line connection failure;
remote controller connection failure; software version mismatch; outdoor unit mismatch
Flow chart
Sub Code 2
Are Main Circuit Board's CN10
And Power Supply Circuit Board's
CN107 Connected Properly?
Sub Code 5
NO
Does No. Of Connected
Remote Controllers Match Supported
No. Of Remote Controllers?
NO
Connect Correct No. Of
Remote Controllers.
YES
YES
Correct Connection.
Remove And Reinsert
Connectors, Then Turn ON
Power Again.
025912-02EN02
Check whether
communication cables
between outdoor and Indoor
units connected properly.
Содержание GYEQ20AN
Страница 1: ...Heat Recovery R 410A 50 Hz GYEQ20 30AN SiAUY361411EA Service Manual Gas Heat Pump Air Conditioner...
Страница 21: ...SiAUY361411EA External Diagrams Device Overview 10 3 External Diagrams GYEQ20AN 3PA003981A Unit mm...
Страница 22: ...External Diagrams SiAUY361411EA 11 Device Overview GYEQ30AN 3PA003980A Unit mm...
Страница 58: ...Installation Work Manual SiAUY361411EA 47 Device Overview 0FGHP EN0801 DGJ002...
Страница 60: ...Installation Work Manual SiAUY361411EA 49 Device Overview 0FGHP EN0801 DGJ002...
Страница 225: ...SiAUY361411EA Maintenance Maintenance Service Data 214...