7 Installing the Outdoor Unit
Heat retention work
z
Be sure to heat-insulate both fluid and gas pipes.
z
Use separate heat insulators to cover the fluid side and gas side pipes. Never use the same heat
insulator to cover both fluid and gas pipes because doing so would result in performance loss and
other problems.
z
Material: Fiberglass or heat-resistant ethylene foam with a thickness of 10 mm or greater and with an
allowable temperature limit of 120 °C or more (gas side) or 70 °C or more (fluid side).
z
Finish with bond, tape or sheet so that the
cut portions and joints of the heat insulators
do not open.
z
When wrapping the heat insulators with
t a p e , t a k e c a r e n o t t o b i n d t h e h e a t
i n s u l a t o r s t o o t i g h t l y, o r t h e y w i l l b e
compressed resulting in poor heat insulation.
z
When wrapping the heat insulators with tape, take care to prevent their cut portions from opening.
Also, take care not to bind the heat insulators too tightly, or they will be compressed resulting in
poor heat insulation.
z
When binding the indoor unit crossover cables together with a refrigerant pipe, lay the cables along
the external surface of the heat insulator. Do not lay the cables inside the heat insulator because
doing so would make the cables contact the refrigerant pipe and thermally deteriorate, resulting in
poor insulation which could cause short circuit problems.
z
Make sure that the link cable does not come into contact with any pipes that do not have a stop valve
or heat insulator.
z
Each pipe joint should be covered with a joint heat insulator and tightly bound with two clamps
(after the air tightness test).
z
Install the heat insulator (standard accessory) to the external filter.
z
The external filter may be replaced. Therefore, the heat retention racking of the external filter should
be fitted so as to allow it to be desorbed.
[Figure of external filter heat insulator]
(Top face)
(Side face)
122
145
145
100
524
(Top face)
(Side face)
325
• For gas pipe
• For fluid pipe
060031-00EN01
Discharge gas pipe
Suction gas pipe
Link
Air conditioner pipe tape
Insulator
Fluid pipe
026731-01E
Содержание GYEQ20AN
Страница 1: ...Heat Recovery R 410A 50 Hz GYEQ20 30AN SiAUY361411EA Service Manual Gas Heat Pump Air Conditioner...
Страница 21: ...SiAUY361411EA External Diagrams Device Overview 10 3 External Diagrams GYEQ20AN 3PA003981A Unit mm...
Страница 22: ...External Diagrams SiAUY361411EA 11 Device Overview GYEQ30AN 3PA003980A Unit mm...
Страница 58: ...Installation Work Manual SiAUY361411EA 47 Device Overview 0FGHP EN0801 DGJ002...
Страница 60: ...Installation Work Manual SiAUY361411EA 49 Device Overview 0FGHP EN0801 DGJ002...
Страница 225: ...SiAUY361411EA Maintenance Maintenance Service Data 214...