Replacement of Primary Parts
Replacement of Parts
210
2.5
Charging the Refrigerant
Caution
Check
page 203 [1 Precautions to Take before Replacement]
before proceeding with the
following steps.
• If the refrigerant is recovered when repairing the refrigerant system or in some other
operation, recharge the refrigerant with the following procedure.
1. Open all of the stop valves and perform evacuation through the stop valves. Turn ON the
outdoor unit evacuation mode when performing evacuation. Be sure to turn OFF the outdoor
unit evacuation mode after the completion of evacuation.
∗
When charging refrigerant after replacing the compressor, cranking or a similar operation
is required. (See
page 206 [2.2 Replacing the Compressor]
.)
2. Turn on the power supply for the indoor and outdoor units and confirm signal transmission
for the indoor and outdoor units.
3. Charge 1 kg of refrigerant from the oil port.
4. Through the gas side stop valve, charge a total amount of refrigerant (initial charged amount
+ on-site charged amount - 1) in the ratio described in the table below, depending on the
outdoor air temperature.
5. Through the liquid side stop valve, charge the remaining full amount.
If you cannot completely charge the remaining amount, close the liquid side stop valve and
charge refrigerant using the additional refrigerant charging mode.
2.6
Removing the Control Box
Caution
Check
page 203 [1. Precautions to Take before Replacement]
before proceeding with the
following steps.
1. Remove the strut on the front left side.
2. Remove the starter transformer, rectifier, and reactor.
3. Remove all harnesses connected to the connectors inside the control box.
∗
Since there are numerous connectors, take photographs or sketches or apply markings
as appropriate to ensure that you can exactly restore the original connections.
4. Remove the bolts that fasten the upper and lower halves of the control box and the control
box base. (The control box splits into upper and lower halves.)
5. Remove the bolts that fasten the control box to the intermediate plate.
6. Pull out the upper and lower halves of the control box.
∗
Take care not to damage the circuit boards and other parts.
[Reverse the steps above to install the replacement]
∗
Make sure that the types and sizes (length in particular) of the bolts and nuts are correct.
∗
Connect connectors while confirming the electrical connection diagram.
Note that connectors are identified by shape and color. The connectors with same shape and
color are identified by labels (such as color or number) on the harness side. Also, the
connectors on the PCB are described with the name of the actuator to be connected, so refer
to the shape, color, label and indication on the PCB and take care not to misconnect the
connectors.
∗
After completing the work, perform an actuator check to check for incorrect wiring.
Outdoor air temperature
0°C or lower
0°C to 30°C
Higher than 30°C
Charged amount
2%
5%
10%
028512-00E01
Example of PCB Description
&RQQHFWRU1R&RORU
$FWXDWRU1DPHDQG1R
WREH&RQQHFWHG
Example of Label
Connector Color to be
&RQQHFWHG
$FWXDWRU1RWREH
&RQQHFWHG
Содержание GYEQ20AN
Страница 1: ...Heat Recovery R 410A 50 Hz GYEQ20 30AN SiAUY361411EA Service Manual Gas Heat Pump Air Conditioner...
Страница 21: ...SiAUY361411EA External Diagrams Device Overview 10 3 External Diagrams GYEQ20AN 3PA003981A Unit mm...
Страница 22: ...External Diagrams SiAUY361411EA 11 Device Overview GYEQ30AN 3PA003980A Unit mm...
Страница 58: ...Installation Work Manual SiAUY361411EA 47 Device Overview 0FGHP EN0801 DGJ002...
Страница 60: ...Installation Work Manual SiAUY361411EA 49 Device Overview 0FGHP EN0801 DGJ002...
Страница 225: ...SiAUY361411EA Maintenance Maintenance Service Data 214...