SiAUY361411EA
Troubleshooting the Outdoor Unit
Troubleshooting
110
1. Troubleshooting the Outdoor Unit
1.1
Error Codes
Your Yanmar Gas Heat Pump system constantly monitors its components for any errors. In the
event that an error has occurred in a unit, the system automatically stops that unit.
When an error occurs, the remote controller connected to the indoor unit notifies you of the error
by displaying the corresponding error code while flashing the run lamp and inspection indicator.
The error codes appears also on the "hour meter" on the outdoor unit's control circuit board.
When normal, the "hour meter" displays operating hours.
Table 4.1/ Error code table
Indoor Unit system
Error
Code
displayed
on
outdoor
unit
Run
lamp
Inspection
indicator
Unit No.
Code
displayed
on
remote
controller
—
Blinking Blinking Blinking
A0
Indoor Unit - External Protection Device Failure
—
Blinking Blinking Blinking
A1
Indoor Unit - P Board Assembly Failure / EEPROM
Misconfigured
—
On
Off
Blinking
A1
Indoor Unit - P Board Assembly Failure
—
Blinking Blinking Blinking
A3
Indoor Unit - Drain Level System Failure
—
Blinking Blinking Blinking
A6
Indoor Unit - Fan Lock
—
On
Off
Blinking
A7
Indoor Unit - Louver Motor (MA) Failure
—
On
Blinking Blinking
A7
Indoor Unit - Louver Motor Failure
—
Blinking Blinking Blinking
A9
Indoor Unit - Electronic Expansion Valve Drive Failure
—
On
Off
Blinking
AF
Indoor Unit - Abnormal Drain
—
On
Off
Blinking
AH
Indoor Unit - Dust Collector Failure
—
Blinking Blinking Blinking
AJ
Indoor Unit - Capacity Setting Incorrect
—
Blinking Blinking Blinking
C1
Indoor Unit - Fan P Board / Adaptor P Board - Control
P Board Transmission Failure
—
Blinking Blinking Blinking
C4
Indoor Unit - Liquid Pipe Thermistor Fault (contact
failure, disconnected, shorted, faulty)
—
Blinking Blinking Blinking
C5
Indoor Unit - Gas Pipe Thermistor Fault (contact
failure, disconnected, shorted, faulty)
—
Blinking Blinking Blinking
C6
Indoor Unit - Fan P Board - Control P Board
Misconfigured
—
Blinking Blinking Blinking
C9
Indoor Unit - Inlet Air Thermistor Fault (contact failure,
disconnected, shorted, faulty)
—
Blinking Blinking Blinking
CA
Indoor Unit - Blow-Out Air Thermistor Fault (contact
failure, disconnected, shorted, faulty)
—
On
Off
Blinking
CE
Indoor Unit / Person Detection / Floor Temperature
Detection Sensor Failure
—
On
Off
Blinking
CJ
Indoor Unit - Remote Control Sensor Failure
E0
Blinking Blinking Blinking
E0
Engine Fails To Start Up
E1
Blinking Blinking Blinking
E1
Engine Overspeed
E2
Blinking Blinking Blinking
E2
Engine Stall
E3
Blinking Blinking Blinking
E3
Oil Pressure Too Low
E4
Blinking Blinking Blinking
E4
Abnormal Cooling Water Temperature
E6
Blinking Blinking Blinking
E6
Abnormal Discharge Temperature
E7
Blinking Blinking Blinking
E7
Abnormal High-Side Pressure
E9
Blinking Blinking Blinking
E9
Abnormal Low-Side Pressure
EA
Blinking Blinking Blinking
EA
Abnormal EEPROM
EH
Blinking Blinking Blinking
EH
Software Version Mismatch / Circuit Board Mismatch
F0
Blinking Blinking Blinking
F0
Starter System Failure
F2
Blinking Blinking Blinking
F2
Outdoor Fan Failure
F3
Blinking Blinking Blinking
F3
Oil Pressure Switch Failure
F4
Blinking Blinking Blinking
F4
Cooling Water Temperature Sensor Disconnected /
Shorted
Содержание GYEQ20AN
Страница 1: ...Heat Recovery R 410A 50 Hz GYEQ20 30AN SiAUY361411EA Service Manual Gas Heat Pump Air Conditioner...
Страница 21: ...SiAUY361411EA External Diagrams Device Overview 10 3 External Diagrams GYEQ20AN 3PA003981A Unit mm...
Страница 22: ...External Diagrams SiAUY361411EA 11 Device Overview GYEQ30AN 3PA003980A Unit mm...
Страница 58: ...Installation Work Manual SiAUY361411EA 47 Device Overview 0FGHP EN0801 DGJ002...
Страница 60: ...Installation Work Manual SiAUY361411EA 49 Device Overview 0FGHP EN0801 DGJ002...
Страница 225: ...SiAUY361411EA Maintenance Maintenance Service Data 214...