Flow Charts for Troubleshooting
SiAUY361411EA
165
Troubleshooting
41
Inter-CPU Communication Failure/
Software Mismatch/Abnormal ROM
Error
code
U2
Description
of the failure
Sub-code 0: Unable to communicate between I/O CPUs for 20 seconds.
Sub-code 2: Unable to communicate between ignition CPUs for 20 seconds.
Sub-code 3: Abnormal I/O CPU ROM
Sub-code 5: Abnormal ignition CPU ROM
Possible
causes
of the failure
CPU program write error; power supply circuit board failure; main circuit board failure; T phase missing
Flow chart
If checker display is
If sub-code 0
If sub-code 2
If sub-code 3 or 5
Software rewritten?
Is the power
supply circuit
board LED1 lit?
Is the power supply
circuit board fuse F4
operating normally?
Is the harness for main
circuit board CN10 and power
supply circuit board CN107
operating normally?
NO
NO
NO
Replace main
circuit board
Replace the
fuse(s)
Replace the
circuit board
Harness
inspection
YES
Replace main
circuit board
YES
Rewrite software
again
YES
YES
Is the supply
voltage normal?
YES
NO
Power supply
voltage inspection
NO
Replace main
circuit board
025909-00EN02
Содержание GYEQ20AN
Страница 1: ...Heat Recovery R 410A 50 Hz GYEQ20 30AN SiAUY361411EA Service Manual Gas Heat Pump Air Conditioner...
Страница 21: ...SiAUY361411EA External Diagrams Device Overview 10 3 External Diagrams GYEQ20AN 3PA003981A Unit mm...
Страница 22: ...External Diagrams SiAUY361411EA 11 Device Overview GYEQ30AN 3PA003980A Unit mm...
Страница 58: ...Installation Work Manual SiAUY361411EA 47 Device Overview 0FGHP EN0801 DGJ002...
Страница 60: ...Installation Work Manual SiAUY361411EA 49 Device Overview 0FGHP EN0801 DGJ002...
Страница 225: ...SiAUY361411EA Maintenance Maintenance Service Data 214...