Troubleshooting the Outdoor Unit
SiAUY361411EA
127
Troubleshooting
[After replacing the mixer, regulator, or engine]
If you have replaced the mixer, regulator, or engine,
clear the initial GVM correction amount
.
• These clearing operations must be performed after replacing the part. For information on the
operating methods, see
page 114 [How to Use the Checker on PCB]
and
page 121 [STOP Mode]
.
NOTE: Be sure to clear the correction amount after replacing these parts. Failing to do so may
cause the engine to stall.
Replacing the main circuit board
Replacing the main circuit board requires the update of the main CPU software and the
reinstallation of the EEPROM on the new main circuit board.
Fig. 4.8/Location of the software update switch and the EEPROM on the main circuit board
1. Before following the replacement procedure, write down the total operating time shown on
the 7-segment hour meter.
2. Turn OFF the outdoor unit's main power supply breaker. Make sure that none of the LEDs
on the circuit board are lit. It is dangerous if there are residual electrical charges.
3. Remote the main circuit board and then remove the EEPROM from the main circuit board.
4. Reinstall the removed EEPROM onto a new main circuit board.
5. Install the new main circuit board into the outdoor unit.
6. Write the main CPU software onto the new main circuit board.
(The main CPU software is not prewritten onto the spare circuit board.)
(1) Connect a PC to the main circuit board. (In the same way as for the PC checker.)
(2) Write the main CPU software.
• Set SW12 on the main circuit board to the "Main CPU writing" side.
• Turn ON the outdoor unit's main power supply breaker and make sure that "P on" is
shown on the 7-segment display.
• Using the writing application installed on the PC, write the main CPU software.
• When finished writing the main CPU software, exit the writing application and turn OFF
the outdoor unit's main power supply breaker.
• Turn SW12 on the main circuit board back to the "Normal" side.
(3) Make sure that the main CPU software is written and runs successfully. Check also that
the version of the written software is correct.
• Turn ON the outdoor unit's main power supply breaker and make sure that "P on" is
shown temporarily on the 7-segment display.
• Check that LED5 on the main circuit board is flashing.
• Make sure that the total operating time on the 7-segment display shows the time you
wrote down at the beginning of this replacement procedure.
• Using the onboard checker, press
and check the version of the main CPU software.
• Make sure that no parts on the circuit board are damaged and that all the connectors
are correctly inserted.
7. Write the version of the written software into the software version entry area of the new main
circuit board.
8. Perform sufficient actuator checks and test runs to ensure that operation is normal.
UP
Содержание GYEQ20AN
Страница 1: ...Heat Recovery R 410A 50 Hz GYEQ20 30AN SiAUY361411EA Service Manual Gas Heat Pump Air Conditioner...
Страница 21: ...SiAUY361411EA External Diagrams Device Overview 10 3 External Diagrams GYEQ20AN 3PA003981A Unit mm...
Страница 22: ...External Diagrams SiAUY361411EA 11 Device Overview GYEQ30AN 3PA003980A Unit mm...
Страница 58: ...Installation Work Manual SiAUY361411EA 47 Device Overview 0FGHP EN0801 DGJ002...
Страница 60: ...Installation Work Manual SiAUY361411EA 49 Device Overview 0FGHP EN0801 DGJ002...
Страница 225: ...SiAUY361411EA Maintenance Maintenance Service Data 214...