SiAUY361411EA
Inspecting the Outdoor Unit
Parts Inspection
184
1.14 Inspecting the Cooling Water Filter
Pinch the rubber hose connected to the cooling water filter, and remove the filter.
Check the mesh in the filter for dirt. If there is any dirt, remove it immediately.
1.15 Checking the Cooling Water System for Water Leaks
Inspecting the radiator cap
While pressurizing the radiator cap with a cap tester, read the graduation of the gauge.
Checking for water leaks
While pressurizing the cooling water passage with a cap tester, read the graduation of the
gauge.
025950-00X
Measuring points
Set value
Radiator cap standard value
0.0490 MPa
Measuring points
Set value
Water leak inspection standard value
No drop in water pressure for 10 minutes at 0.13 MPa.
025951-00E
Cap tester
Cap
025952-00E
Cap tester
Attachment adapt
o
r
Radiator cap