Inspecting the Outdoor Unit
SiAUY361411EA
171
Parts Inspection
1.2
Inspecting the Starter System
Activation timing
Output voltage
∗
This should be tested approximately 10 minutes after stopping (because the voltage
immediately after stopping will be the same as while running).
1. Using a tester, check if the output voltage requirements specified above are met.
2. If the voltage is significantly different than specified above, stop the system using the
onboard checker and wait for 5 minutes; then, with the power OFF, check the harness for
continuity and the junction connectors for contact failure using a tester.
3. If the harness and connectors are OK, then check each component.
[Note]
Perform voltage checks by applying a tester to the back face of each connector, rather
than unplugging the connector.
Fuses on the harness
Inspect the fuses on the harness to make sure they are not blown.
Inspecting the starter transformer
Inspect the transformer by measuring the resistance between its terminals.
∗
At 20°C (reference value)
Inspecting the reactor
Inspect the reactor by measuring the resistance between its terminals.
∗
At 20°C (reference value)
Parts to
inspect
Measuring points
During system stop After
startup (while running)
At system startup
(with actuator CH01
ON)
Transformer
relay
Between power supply circuit
board's RY8 terminals
During stop: No continuity
∗
While running: Continuity exists
Continuity exists
Starter
transformer
Between R and T terminals on
the primary side
During stop: 0 V
∗
While running: 200 V AC
200 V AC
Self-starter
motor
Between S terminal and
ground
During stop: 0 V
While running: 0 V
12 V DC
Between B terminal and
ground
During stop: 0 V
While running: 12 V DC
12 V DC
Part
Purpose
Capacity
On the
harness
For S terminal
32 V DC/30 A
For M terminal
32 V DC/3 A
Measuring points
Measured value
∗
Between red and black terminals on the primary side
520 m
Ω
Between blue terminals on the secondary side
40 m
Ω
Measuring points
Model
Measured value (
Ω
)
∗
Between terminals
∗
GYEQ20AN
0.17
GYEQ30AN
0.06
ON
OFF
ON
OFF
Power
ON
System
startup
Startup
complete
System
stop
Actuator
check
CH01:OFF
Actuator
check
CH01:ON
Transformer relay (RY8)
Starter relay (RY3)
023303-00E
After approx. 10 min
Содержание GYEQ20AN
Страница 1: ...Heat Recovery R 410A 50 Hz GYEQ20 30AN SiAUY361411EA Service Manual Gas Heat Pump Air Conditioner...
Страница 21: ...SiAUY361411EA External Diagrams Device Overview 10 3 External Diagrams GYEQ20AN 3PA003981A Unit mm...
Страница 22: ...External Diagrams SiAUY361411EA 11 Device Overview GYEQ30AN 3PA003980A Unit mm...
Страница 58: ...Installation Work Manual SiAUY361411EA 47 Device Overview 0FGHP EN0801 DGJ002...
Страница 60: ...Installation Work Manual SiAUY361411EA 49 Device Overview 0FGHP EN0801 DGJ002...
Страница 225: ...SiAUY361411EA Maintenance Maintenance Service Data 214...