SiAUY361411EA
Control Overview
Control and Functionality
96
1.4
Setting Up and Rewiring the Outdoor Unit
Configuring the outdoor unit DIP switches
Caution
Before accessing the DIP switches, turn off the power and make sure that none of the LEDs on
the circuit board are lit. Attempting to access the DIP switches with any LED lit could result in an
electrical shock due to electricity remaining in the circuit.
Caution
After changing any DIP switch setting or connector, you have to turn the power off and back on
for the new setting to take effect.
[Configuring the DIP switches on the main circuit board]
Refer to “3. Setting and Rewiring the Outdoor Unit” in Wiring Manual on page 63.
Table 3.4/ Configuring the DIP switches on the DCBL circuit board
Configuring the switches on the BS unit
Table 3.5/ Configuring the switches on the BS unit
Be sure to check the DIP switch settings regardless of whether or not you want to change the factory
default settings.
After changing any DIP switch setting or connector, you have to turn the power off and back on for
the new setting to take effect.
When you want to reset the outdoor unit power supply, turn off the power and make sure that none
of the LEDs on the circuit board are lit before turning back on the power. An attempt to reset the
power supply with any LED lit may fail due to electricity remaining in the circuit.
Name
SW
No.
Switch
position
Applicable
Factory
default
On-site
configuration
Remarks
DS1
1
OFF
{
All OFF
Cannot be
changed
Must be
always OFF.
2
OFF
3
OFF
4
OFF
• You have to configure these switches when you use a heating/cooling switching remote controller
or centralized cooling/heating remote controller.
• Be sure to configure the switches before turning ON the power since they are read by the
microcomputer upon power ON.
• When you are finished configuring the switches, be sure to close the electrical box cover.
To use a heating/cooling switching remote controller:
To use a heating/cooling switching remote controller,
connect to terminal (A), (B), and (C) located on the circuit
board contained in the BS unit electrical box.
To use a centralized cooling/heating remote controller (an optional outdoor unit external control
adaptor is required):
To use a centralized cooling/heating remote controller,
connect the connector of the outdoor unit external control
adaptor to connector CN18 located on the circuit board
contained in the electrical box.
DS1
ON
OFF
Turn on DS1-2.
028154-00E
1 2 3 4
DS1
ON
OFF
Turn on DS1-1
028155-00E
1 2 3 4
Содержание GYEQ20AN
Страница 1: ...Heat Recovery R 410A 50 Hz GYEQ20 30AN SiAUY361411EA Service Manual Gas Heat Pump Air Conditioner...
Страница 21: ...SiAUY361411EA External Diagrams Device Overview 10 3 External Diagrams GYEQ20AN 3PA003981A Unit mm...
Страница 22: ...External Diagrams SiAUY361411EA 11 Device Overview GYEQ30AN 3PA003980A Unit mm...
Страница 58: ...Installation Work Manual SiAUY361411EA 47 Device Overview 0FGHP EN0801 DGJ002...
Страница 60: ...Installation Work Manual SiAUY361411EA 49 Device Overview 0FGHP EN0801 DGJ002...
Страница 225: ...SiAUY361411EA Maintenance Maintenance Service Data 214...