Inspecting the Outdoor Unit
SiAUY361411EA
195
Parts Inspection
1.29 Inspecting the Electronic Expansion Valve
Inspect the electronic expansion valve by measuring the resistance of its coil.
Measuring points
Measured value
Between terminals #1 (red) and #4 (white)
46
Ω
Between terminals #1 (red) and #6 (amber)
46
Ω
Between terminals #1 (red) and #5 (yellow)
46
Ω
Between terminals #1 (red) and #7 (blue)
46
Ω
6 5 4 3 2 1
7
Blue
Amber
Yellow
White
(Not used)
(Not used)
Red
Circuit No. indication
White
(COM) Red
Amber
Yellow
Blue
Red
(
COM
)
ø1
ø2 ø4
ø3
023464-00E