Inspecting the Outdoor Unit
SiAUY361411EA
177
Parts Inspection
Inspecting the ignition coil
Inspect the ignition coil by measuring the resistance between its primary side terminals.
[Caution]
• Check if the plug caps and cords are correctly connected.
• Check if the primary side terminal connectors are in perfect contact.
Inspecting the crank pulse sensor
Inspect the crank pulse sensor by measuring the resistance between its terminals. Check the
sensor and flywheel for any gap.
Inspecting the cam pulse sensor
Inspect the cam pulse sensor by measuring the resistance between its terminals.
[Note]
No gap adjustment is required for the cam pulse sensor.
Measuring points
Measured value
Between terminals
0.7
Ω
Measuring points
Measured value
Between terminals
515±35
Ω
Gap between sensor and flywheel
0.7 to 1.1 mm
∗
Make sure that the starter cable is not running close.
If so, fix it using clamps to keep a distance.
Measuring points
Measured value
Between terminals
515±35
Ω
Coupler
Part No., NGK item No.
Primary power
output (V-)
Primary power
output (V+)
Secondary power
output
V
2
out
023461-00E
025945-00E01
025946-00X
Содержание GYEQ20AN
Страница 1: ...Heat Recovery R 410A 50 Hz GYEQ20 30AN SiAUY361411EA Service Manual Gas Heat Pump Air Conditioner...
Страница 21: ...SiAUY361411EA External Diagrams Device Overview 10 3 External Diagrams GYEQ20AN 3PA003981A Unit mm...
Страница 22: ...External Diagrams SiAUY361411EA 11 Device Overview GYEQ30AN 3PA003980A Unit mm...
Страница 58: ...Installation Work Manual SiAUY361411EA 47 Device Overview 0FGHP EN0801 DGJ002...
Страница 60: ...Installation Work Manual SiAUY361411EA 49 Device Overview 0FGHP EN0801 DGJ002...
Страница 225: ...SiAUY361411EA Maintenance Maintenance Service Data 214...